Assessment Year | 1999 |
---|---|
Principal Product | plows |
NAICS |
n/a
|
SIC | 3599: Industrial and Commercial Machinery and Equipment, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 34 |
Plant Area |
63,475
ft2
|
Annual Production | 80
pieces
|
Production Hrs. Annual | 2,565
hrs
|
Location (State) | Maine |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $34,954 | 463,658 |
kWh
|
$0.075 |
Electricity Demand | $21,844 | 2,661 |
kW-mo/yr
|
$8.21 |
Electricity Fees | $2,083 | - |
|
- |
LPG | $133 | 8 |
MMBtu
|
$16.63 |
Fuel Oil #2 | $15,539 | 4,254 |
MMBtu
|
$3.65 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $24,887 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $16,105 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Fuel Oil #2 Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7492: Use proper thickness of insulation on building envelope | $7,431 | $1,766 | - | - | - |
$7,431
-
MMBtu
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,530 | $17,411 |
$4,186
55,686
kWh
|
$2,344
-
kW-mo/yr
|
- | - | - | |
03 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $4,209 | $8,532 |
$2,728
36,342
kWh
|
$2,065
-
kW-mo/yr
|
- |
$(-584.0)
-
MMBtu
|
- | |
04 | 4.446: Automate finishing process | $2,640 | $5,225 | - | - | - | - | $2,640 | |
05 | 4.445: Install equipment to move product | $1,375 | $2,000 | - | - | - | - | $1,375 | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $917 | $150 |
$917
12,309
kWh
|
- | - | - | - | |
07 | 2.8121: Apply for tax-free status for energy purchases | $711 | - | - | - | - | - | $711 | |
08 | 4.651: Install back-up equipment | $516 | $300 |
$(-121.0)
(-1,758)
kWh
|
$(-21.0)
-
kW-mo/yr
|
- | - | $658 | |
09 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $558 | $826 |
$748
9,965
kWh
|
$472
-
kW-mo/yr
|
$(-662.0)
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $24,887 | $36,210 |
$8,458
112,544
kWh
|
$4,860
-
kW-mo/yr
|
$(-662.0)
-
MMBtu
|
$6,847
-
MMBtu
|
$5,384 | ||
TOTAL IMPLEMENTED | $16,105 | $19,627 |
$4,982
66,237
kWh
|
$2,323
-
kW-mo/yr
|
- |
$7,431
-
MMBtu
|
$1,369 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Fuel Oil #2 Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs