Assessment Year | 1998 |
---|---|
Principal Product | ball valves and actuators |
NAICS |
n/a
|
SIC | 3494: Valves and Pipe Fittings, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 45 |
Plant Area |
87,500
ft2
|
Annual Production | 100,000
pieces
|
Production Hrs. Annual | 4,125
hrs
|
Location (State) | New Hampshire |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $69,746 | 565,944 |
kWh
|
$0.12 |
Electricity Demand | $16,719 | 2,022 |
kW-mo/yr
|
$8.27 |
LPG | $17,919 | 2,531 |
MMBtu
|
$7.08 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $26,969 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Other Liquid (haz) Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,883 | $25,900 | n/a |
$6,973
77,374
kWh
|
$1,910
-
kW-mo/yr
|
- | - | - |
02 | 2.4133: Use most efficient type of electric motors | $1,601 | $14,083 | n/a |
$986
10,844
kWh
|
$615
-
kW-mo/yr
|
- | - | - |
03 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $1,320 | $2,600 | n/a |
$578
4,689
kWh
|
$893
-
kW-mo/yr
|
$(-151.0)
-
MMBtu
|
- | - |
04 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $911 | $450 | n/a |
$881
9,672
kWh
|
$446
-
kW-mo/yr
|
$(-416.0)
-
MMBtu
|
- | - |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $830 | $500 | n/a |
$830
9,086
kWh
|
- | - | - | - |
06 | 2.4221: Install compressor air intakes in coolest locations | $304 | $300 | n/a |
$304
3,224
kWh
|
- | - | - | - |
07 | 3.3131: Use evaporation to concentrate material | $6,872 | $17,050 | n/a | - | - |
$(-1,295.0)
-
MMBtu
|
$8,167
-
gal
|
- |
08 | 3.3133: Use other waste concentration methods | $6,248 | $6,950 | n/a | - | - | - | - | $6,248 |
TOTAL RECOMMENDED | $26,969 | $67,833 |
$10,552
114,889
kWh
|
$3,864
-
kW-mo/yr
|
$(-1,862.0)
-
MMBtu
|
$8,167
-
gal
|
$6,248 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings | Other Liquid (haz) Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs