Assessment Year | 2023 |
---|---|
Principal Product | Aerospace Sensors |
NAICS | 334511: Search, Detection, Navigation, Guidance, Aeronautical, and Nautical System and Instrument Manufactur |
SIC | 3829: Measuring and Controlling Devices, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 61 |
Plant Area |
78,000
ft2
|
Annual Production | 50,000
units
|
Production Hrs. Annual | 3,120
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $196,045 | 1,947,840 |
kWh
|
$0.10 |
Electricity Demand | $39,177 | 4,897 |
kW-mo/yr
|
$8.00 |
Electricity Fees | $(-3,086.0) | - |
|
- |
Natural Gas | $24,820 | 1,773 |
MMBtu
|
$14.00 |
TOTAL YEARLY COSTS | $256,956 | |||
RECOMMENDED SAVINGS* | $24,917 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $12,177 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,825 | $12,405 |
$5,233
51,816
kWh
|
$1,592
-
kW-mo/yr
|
- | |
02 | 2.7314: Reduce ventilation air | $4,889 | $35,240 |
$583
5,768
kWh
|
$176
-
kW-mo/yr
|
$4,130
-
MMBtu
|
|
03 | 2.4322: Use or replace with energy efficient substitutes | $4,725 | $7,950 |
$3,621
35,855
kWh
|
$1,104
-
kW-mo/yr
|
- | |
04 | 2.7135: Install occupancy sensors | $3,953 | $6,018 |
$3,953
39,137
kWh
|
- | - | |
05 | 2.6231: Utilize controls to operate equipment only when needed | $3,126 | $1,425 |
$2,398
23,740
kWh
|
$728
-
kW-mo/yr
|
- | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,399 | $3,125 |
$1,072
10,617
kWh
|
$327
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $24,917 | $66,163 |
$16,860
166,933
kWh
|
$3,927
-
kW-mo/yr
|
$4,130
-
MMBtu
|
||
TOTAL IMPLEMENTED | $12,177 | $21,548 |
$10,258
101,570
kWh
|
$1,919
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs