| Assessment Year | 2014 |
|---|---|
| Principal Product | Steering columns |
| NAICS | 336330: Motor Vehicle Steering and Suspension Components (except Spring) Manufacturing |
| SIC | 3714: Motor Vehicle Parts and Accessories |
| Sales Range | $50 M to 100M |
| # of Employees | 248 |
| Plant Area |
165,000
ft2
|
| Annual Production | 810,000
pieces
|
| Production Hrs. Annual | 7,200
hrs
|
| Location (State) | Vermont |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $457,915 | 6,696,549 |
kWh
|
$0.068 |
| Electricity Demand | $241,330 | 52,066 |
kW-mo/yr
|
$4.64 |
| Electricity Fees | $79,845 | - |
|
- |
| LPG | $109,687 | 6,181 |
MMBtu
|
$17.75 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $32,377 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $608 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | LPG Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7235: Install fossil fuel make-up air unit | $25,418 | $110,000 | - |
$25,418
-
MMBtu
|
|
| 02 | 2.6218: Turn off equipment when not in use | $3,232 | $500 |
$3,232
47,257
kWh
|
- | |
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,119 | $5,375 |
$3,119
45,606
kWh
|
- | |
| 04 | 2.7264: Interlock heating and air conditioning systems to prevent simultaneous operation | $608 | $500 |
$289
4,224
kWh
|
$319
-
MMBtu
|
|
| TOTAL RECOMMENDED | $32,377 | $116,375 |
$6,640
97,087
kWh
|
$25,737
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $608 | $500 |
$289
4,224
kWh
|
$319
-
MMBtu
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs