Assessment Year | 2008 |
---|---|
Principal Product | Semiconductors |
NAICS | 334413: Semiconductor and Related Device Manufacturing |
SIC | 3674: Semiconductors and Related Devices |
Sales Range | $50 M to 100M |
# of Employees | 437 |
Plant Area |
160,000
ft2
|
Annual Production | 100,000,000
pieces
|
Production Hrs. Annual | 5,228
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,725,540 | 13,025,400 |
kWh
|
$0.13 |
Electricity Demand | $178,335 | 29,430 |
kW-mo/yr
|
$6.06 |
Electricity Fees | $840 | - |
|
- |
Natural Gas | $222,698 | 18,335 |
MMBtu
|
$12.15 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $67,869 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $52,019 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7314: Reduce ventilation air | $36,692 | $39,000 |
$25,587
198,015
kWh
|
- |
$11,105
-
MMBtu
|
- | |
02 | 2.3212: Optimize plant power factor | $11,811 | $11,850 | - |
$11,811
-
kW-mo/yr
|
- | - | |
03 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $11,640 | $43,000 |
$11,640
87,842
kWh
|
- | - | - | |
04 | 3.4151: Minimize water usage | $4,210 | $18,000 | - | - | - |
$4,210
-
Tgal
|
|
05 | 2.7261: Install timers and/or thermostats | $1,895 | $3,000 | - | - |
$1,895
-
MMBtu
|
- | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $977 | - |
$876
6,610
kWh
|
$101
-
kW-mo/yr
|
- | - | |
07 | 2.2136: Install / repair insulation on steam lines | $644 | $689 | - | - |
$644
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $67,869 | $115,539 |
$38,103
292,467
kWh
|
$11,912
-
kW-mo/yr
|
$13,644
-
MMBtu
|
$4,210
-
Tgal
|
||
TOTAL IMPLEMENTED | $52,019 | $54,539 |
$26,463
204,625
kWh
|
$11,912
-
kW-mo/yr
|
$13,644
-
MMBtu
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs