Assessment Year | 2011 |
---|---|
Principal Product | Aseptically Packaged Products |
NAICS | 311999: All Other Miscellaneous Food Manufacturing |
SIC | 2032: Canned Specialties |
Sales Range | $50 M to 100M |
# of Employees | 112 |
Plant Area |
171,000
ft2
|
Annual Production | 90,000,000
lb
|
Production Hrs. Annual | 7,200
hrs
|
Location (State) | Wisconsin |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $364,113 | 6,865,806 |
kWh
|
$0.053 |
Electricity Demand | $159,217 | 36,690 |
kW-mo/yr
|
$4.34 |
Natural Gas | $820,110 | 145,580 |
MMBtu
|
$5.63 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $137,352 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $10,158 | $15,702 |
$8,502
160,400
kWh
|
$1,656
-
kW-mo/yr
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,704 | $16,590 |
$10,179
192,020
kWh
|
$1,525
-
kW-mo/yr
|
- | |
03 | 2.7135: Install occupancy sensors | $2,818 | $1,530 |
$2,818
53,153
kWh
|
- | - | |
04 | 2.2628: Utilize a less expensive cooling method | $59,656 | $20,000 |
$59,656
1,125,600
kWh
|
- | - | |
05 | 2.2437: Recover waste heat from equipment | $15,983 | $25,000 | - | - |
$15,983
-
MMBtu
|
|
06 | 2.4239: Eliminate or reduce compressed air usage | $1,698 | $240 |
$1,208
22,800
kWh
|
$490
-
kW-mo/yr
|
- | |
07 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,593 | $250 |
$6,689
126,216
kWh
|
$904
-
kW-mo/yr
|
- | |
08 | 2.2612: Use cooling tower water instead of refrigeration | $22,774 | $1,500 |
$22,774
429,696
kWh
|
- | - | |
09 | 2.2442: Preheat combustion air with waste heat | $3,450 | $1,000 | - | - |
$3,450
-
MMBtu
|
|
10 | 2.6212: Turn off equipment during breaks, reduce operating time | $1,518 | $200 |
$1,518
28,646
kWh
|
- | - | |
TOTAL RECOMMENDED | $137,352 | $82,012 |
$113,344
2,138,531
kWh
|
$4,575
-
kW-mo/yr
|
$19,433
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs