| Assessment Year | 2008 |
|---|---|
| Principal Product | Rifles and shotguns |
| NAICS | 332994: Small Arms, Ordnance, and Ordnance Accessories Manufacturing |
| SIC | 3484: Small Arms |
| Sales Range | $50 M to 100M |
| # of Employees | 268 |
| Plant Area |
317,000
ft2
|
| Annual Production | 151,000
pieces
|
| Production Hrs. Annual | 4,420
hrs
|
| Location (State) | Massachusetts |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $456,042 | 3,974,400 |
kWh
|
$0.11 |
| Electricity Demand | $42,752 | 10,068 |
kW-mo/yr
|
$4.25 |
| Electricity Fees | $2,712 | - |
|
- |
| Natural Gas | $274,631 | 17,097 |
MMBtu
|
$16.06 |
| Fuel Oil #2 | $65,772 | 3,829 |
MMBtu
|
$17.18 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $49,943 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $35,444 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $33,014 | $119,495 |
$30,154
262,900
kWh
|
$2,860
-
kW-mo/yr
|
- | - | |
| 02 | 2.2427: Use waste heat from hot flue gases to preheat incoming fluids | $11,407 | $20,000 | - | - |
$11,407
-
MMBtu
|
- | |
| 03 | 2.1113: Reduce combustion air flow to optimum | $2,058 | $3,000 | - | - |
$2,058
-
MMBtu
|
- | |
| 04 | 2.7232: Replace existing hvac unit with high efficiency model | $1,932 | $2,500 |
$262
2,300
kWh
|
- | - |
$1,670
-
gal
|
|
| 05 | 2.7251: Reduce air conditioning load by evaporating water from roof | $1,034 | $6,000 |
$1,034
9,105
kWh
|
- | - | - | |
| 06 | 2.2136: Install / repair insulation on steam lines | $498 | $500 | - | - |
$498
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $49,943 | $151,495 |
$31,450
274,305
kWh
|
$2,860
-
kW-mo/yr
|
$13,963
-
MMBtu
|
$1,670
-
gal
|
||
| TOTAL IMPLEMENTED | $35,444 | $122,495 |
$30,416
265,200
kWh
|
$2,860
-
kW-mo/yr
|
$498
-
MMBtu
|
$1,670
-
gal
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs