ITAC Assessment: MA0629
ITAC logo
ITAC Assessment: MA0629
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2008
Principal Product Metering pumps
NAICS 333911: Pump and Pumping Equipment Manufacturing
SIC 3651: Household Audio and Video Equipment
Sales Range $10
M
to 50
M
# of Employees 109
Plant Area 50,500
ft2
Annual Production 130,000
pieces
Production Hrs. Annual 4,940
hrs
Location (State) Massachusetts

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $153,530 1,066,344
kWh
Electricity Demand $55,703 2,871
kW-mo/yr
Electricity Fees $2,964 -
Natural Gas $19,069 1,160
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $11,439 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $6,411

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.7221: Lower temperature during the winter season and vice-versa $5,363 $2,800 - - $5,363
-
MMBtu
02 2.3212: Optimize plant power factor $1,935 $2,100 - $1,935
-
kW-mo/yr
-
03 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $1,726 $6,800 $1,726
12,000
kWh
- -
04 2.7293: Install dry sprinkler system or other method to reduce heating requirements $1,367 $3,000 $1,367
9,500
kWh
- -
05 2.7243: Improve air circulation with destratification fans / other methods $450 $1,620 $(-93.0)
(-650)
kWh
- $543
-
MMBtu
06 2.4221: Install compressor air intakes in coolest locations $351 $400 $351
2,441
kWh
- -
07 2.2136: Install / repair insulation on steam lines $247 $200 - - $247
-
MMBtu
TOTAL RECOMMENDED $11,439 $16,920 $3,351
23,291
kWh
$1,935
-
kW-mo/yr
$6,153
-
MMBtu
TOTAL IMPLEMENTED $6,411 $5,020 $258
1,791
kWh
- $6,153
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs