*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2007
Principal Product HID ligh bulbs
NAICS 335122: Commercial, Industrial, and Institutional Electric Lighting Fixture Manufacturing
SIC 3646: Commercial, Industrial, and Institutional Electric Lighting Fixtures
Sales Range $100
M
to 500
M
# of Employees 575
Plant Area 255,000
ft2
Annual Production 10,000,000
pieces
Production Hrs. Annual 8,256
hrs
Location (State) New Hampshire

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,886,955 18,148,382
kWh
Electricity Demand $242,844 33,905
kW-mo/yr
Electricity Fees $9,558 -
Natural Gas $336,768 30,653
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $427,215 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $69,033

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings Primary Raw Material Savings
01 4.631: Install an uninteruptable power supply $227,962 $1,200,000 $(-107,328.0)
(-1,032,000)
kWh
$10,740
-
kW-mo/yr
$(-450.0)
-
MMBtu
$325,000 -
02 4.132: Purchase new equipment to reduce material use / cost $93,033 $350,000 $(-19,063.0)
(-183,300)
kWh
$(-1,904.0)
-
kW-mo/yr
- - $114,000
03 2.4239: Eliminate or reduce compressed air usage $42,349 $10,800 $42,349
407,200
kWh
- - - -
04 2.7241: Install outside air damper / economizer on hvac unit $15,153 $5,154 $14,258
137,100
kWh
$895
-
kW-mo/yr
- - -
05 2.2614: Use cooling tower or economizer to replace chiller cooling $14,883 $5,300 $13,601
130,778
kWh
$1,282
-
kW-mo/yr
- - -
06 2.7314: Reduce ventilation air $14,409 $11,500 $364
3,500
kWh
- $14,045
-
MMBtu
- -
07 2.7243: Improve air circulation with destratification fans / other methods $8,715 $19,440 $(-1,747.0)
(-16,800)
kWh
$(-165.0)
-
kW-mo/yr
$10,627
-
MMBtu
- -
08 2.4221: Install compressor air intakes in coolest locations $7,151 $7,151 $6,500
62,900
kWh
$651
-
kW-mo/yr
- - -
09 2.7221: Lower temperature during the winter season and vice-versa $3,560 $1,184 - - $3,560
-
MMBtu
- -
TOTAL RECOMMENDED $427,215 $1,610,529 $(-51,066.0)
(-490,622)
kWh
$11,499
-
kW-mo/yr
$27,782
-
MMBtu
$325,000 $114,000
TOTAL IMPLEMENTED $69,033 $42,924 $40,966
393,900
kWh
$(-165.0)
-
kW-mo/yr
$28,232
-
MMBtu
- -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings Primary Raw Material Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs