Assessment Year | 2006 |
---|---|
Principal Product | Converted paper, foil and film |
NAICS | 322220: Paper Bag and Coated and Treated Paper Manufacturing |
SIC | 2672: Coated and Laminated Paper, Not Elsewhere Classified |
Sales Range | $50 M to 100M |
# of Employees | 195 |
Plant Area |
261,000
ft2
|
Annual Production | 691,335
pieces
|
Production Hrs. Annual | 7,344
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $430,203 | 6,047,530 |
kWh
|
$0.071 |
Electricity Demand | $79,155 | 13,364 |
kW-mo/yr
|
$5.92 |
Electricity Fees | $3,432 | - |
|
- |
Natural Gas | $521,600 | 61,959 |
MMBtu
|
$8.42 |
Fuel Oil #2 | $79,027 | 7,042 |
MMBtu
|
$11.22 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $197,508 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $37,536 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.2437: Recover waste heat from equipment | $79,413 | $172,300 |
$(-7,946.0)
(-111,700)
kWh
|
$(-2,241.0)
-
kW-mo/yr
|
$89,600
-
MMBtu
|
|
02 | 2.2212: Use minimum safe oven ventilation | $71,115 | $115,075 |
$(-4,977.0)
(-69,800)
kWh
|
$(-784.0)
-
kW-mo/yr
|
$76,876
-
MMBtu
|
|
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $19,335 | $96,992 |
$17,019
238,700
kWh
|
$2,316
-
kW-mo/yr
|
- | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $8,691 | $749 |
$7,622
106,900
kWh
|
$1,069
-
kW-mo/yr
|
- | |
05 | 2.2511: Insulate bare equipment | $8,388 | $4,050 | - | - |
$8,388
-
MMBtu
|
|
06 | 2.6231: Utilize controls to operate equipment only when needed | $7,526 | $8,755 |
$1,290
18,100
kWh
|
- |
$6,236
-
MMBtu
|
|
07 | 2.3212: Optimize plant power factor | $1,918 | $700 |
$1,518
21,300
kWh
|
$400
-
kW-mo/yr
|
- | |
08 | 2.2511: Insulate bare equipment | $1,122 | $950 | - | - |
$1,122
-
MMBtu
|
|
TOTAL RECOMMENDED | $197,508 | $399,571 |
$14,526
203,500
kWh
|
$760
-
kW-mo/yr
|
$182,222
-
MMBtu
|
||
TOTAL IMPLEMENTED | $37,536 | $102,741 |
$24,641
345,600
kWh
|
$3,385
-
kW-mo/yr
|
$9,510
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs