Assessment Year | 2004 |
---|---|
Principal Product | Bread based food products |
NAICS | 311821: Cookie and Cracker Manufacturing |
SIC | 2050: |
Sales Range | $50 M to 100M |
# of Employees | 220 |
Plant Area |
250,000
ft2
|
Annual Production | 19,200,000
lb
|
Production Hrs. Annual | 4,080
hrs
|
Location (State) | New York |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $399,602 | 3,854,400 |
kWh
|
$0.10 |
Electricity Demand | $205,361 | 11,336 |
kW-mo/yr
|
$18.12 |
Electricity Fees | $(-49,202.0) | - |
|
- |
Natural Gas | $669,743 | 73,364 |
MMBtu
|
$9.13 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $193,448 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $37,186 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 4.652: Replace existing equipment with more suitable substitutes | $93,689 | $21,360 |
$(-2,311.0)
(-21,600)
kWh
|
- | - | - | $96,000 | |
02 | 2.2414: Use waste heat from hot flue gases to preheat | $17,401 | $31,625 | - | - |
$17,401
-
MMBtu
|
- | - | |
03 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $14,380 | $4,000 | - | - | - |
$14,380
-
Tgal
|
- | |
04 | 2.7261: Install timers and/or thermostats | $7,043 | $4,730 | - | - |
$7,043
-
MMBtu
|
- | - | |
05 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $5,846 | $17,600 | - | - |
$5,846
-
MMBtu
|
- | - | |
06 | 2.2136: Install / repair insulation on steam lines | $5,209 | $1,643 | - | - |
$5,209
-
MMBtu
|
- | - | |
07 | 2.2136: Install / repair insulation on steam lines | $2,686 | $285 | - | - |
$2,686
-
MMBtu
|
- | - | |
08 | 2.4235: Remove or close off unneeded compressed air lines | $428 | $18,000 |
$428
4,000
kWh
|
- | - | - | - | |
09 | 2.7135: Install occupancy sensors | $31,340 | $3,749 |
$31,340
293,100
kWh
|
- | - | - | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $15,426 | $49,385 |
$14,006
130,900
kWh
|
$1,420
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $193,448 | $152,377 |
$43,463
406,400
kWh
|
$1,420
-
kW-mo/yr
|
$38,185
-
MMBtu
|
$14,380
-
Tgal
|
$96,000 | ||
TOTAL IMPLEMENTED | $37,186 | $21,349 |
$31,340
293,100
kWh
|
- |
$5,846
-
MMBtu
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs