Assessment Year 2003
Principal Product Corrugated boxes
NAICS 322211: Corrugated and Solid Fiber Box Manufacturing
SIC 2653: Corrugated and Solid Fiber Boxes
Sales Range $10
M
to 50
M
# of Employees 130
Plant Area 200,000
ft2
Annual Production 637,000
thousand feet
Production Hrs. Annual 4,160
hrs
Location (State) Massachusetts

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $300,406 4,138,000
kWh
Electricity Demand $70,454 12,330
kW-mo/yr
Electricity Fees $807 -
Natural Gas $104,497 11,119
MMBtu
Fuel Oil #2 $133,200 28,456
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $71,845 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $28,310

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Fuel Oil #2 Savings Water Consumption Savings
01 2.7221: Lower temperature during the winter season and vice-versa $27,237 $1,300 - - $27,237
-
MMBtu
- -
02 2.7314: Reduce ventilation air $16,298 $34,450 - - $16,298
-
MMBtu
- -
03 2.2128: Use steam condensate for hot water supply (non-potable) $10,803 $25,625 - - $9,406
-
MMBtu
$1,151
-
MMBtu
$246
-
Tgal
04 2.7131: Add area lighting switches $8,645 $3,215 $8,645
131,789
kWh
- - - -
05 2.3212: Optimize plant power factor $5,140 $15,455 - $5,140
-
kW-mo/yr
- - -
06 2.7243: Improve air circulation with destratification fans / other methods $2,624 $6,120 $(-628.0)
(-8,966)
kWh
$(-42.0)
-
kW-mo/yr
$3,294
-
MMBtu
- -
07 2.4221: Install compressor air intakes in coolest locations $1,098 $1,090 $1,098
14,482
kWh
- - - -
TOTAL RECOMMENDED $71,845 $87,255 $9,115
137,305
kWh
$5,098
-
kW-mo/yr
$56,235
-
MMBtu
$1,151
-
MMBtu
$246
-
Tgal
TOTAL IMPLEMENTED $28,310 $51,505 $9,115
137,305
kWh
$5,098
-
kW-mo/yr
$12,700
-
MMBtu
$1,151
-
MMBtu
$246
-
Tgal
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Fuel Oil #2 Savings Water Consumption Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs