Assessment Year 2000
Principal Product Venting for fireplaces and boilers
NAICS
n/a
SIC 3499: Fabricated Metal Products, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 76
Plant Area 130,000
ft2
Annual Production 500,000
pieces
Production Hrs. Annual 4,420
hrs
Location (State) Massachusetts

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $72,966 1,165,592
kWh
Electricity Demand $26,141 3,571
kW-mo/yr
Electricity Fees $8,834 -
Natural Gas $23,312 2,783
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $13,632 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $8,469

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings
01 2.8121: Apply for tax-free status for energy purchases $4,970 $500 - - - $4,970
02 2.7231: Use radiant heater for spot heating $3,064 $12,000 $526
8,206
kWh
- $2,538
-
MMBtu
-
03 2.2614: Use cooling tower or economizer to replace chiller cooling $2,099 $4,500 $1,682
26,377
kWh
$417
-
kW-mo/yr
- -
04 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,495 $365 $1,495
23,447
kWh
- - -
05 2.4224: Upgrade controls on compressors $1,402 $280 $1,402
21,981
kWh
- - -
06 2.4231: Reduce the pressure of compressed air to the minimum required $396 $280 $299
4,689
kWh
$97
-
kW-mo/yr
- -
07 2.4221: Install compressor air intakes in coolest locations $206 $450 $206
3,224
kWh
- - -
TOTAL RECOMMENDED $13,632 $18,375 $5,610
87,924
kWh
$514
-
kW-mo/yr
$2,538
-
MMBtu
$4,970
TOTAL IMPLEMENTED $8,469 $1,875 $3,402
53,341
kWh
$97
-
kW-mo/yr
- $4,970
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Administrative Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs