Assessment Year 2000
Principal Product Stationary Products
NAICS
n/a
SIC 2678: Stationery, Tablets, and Related Products
Sales Range $10
M
to 50
M
# of Employees 475
Plant Area 200,000
ft2
Annual Production 90,000,000
lb
Production Hrs. Annual 6,240
hrs
Location (State) Massachusetts

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $207,678 3,713,951
kWh
Electricity Demand $20,461 7,930
kW-mo/yr
Electricity Fees $3,468 -
Natural Gas $43,067 5,373
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $34,279 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $30,162

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.7224: Reduce space conditioning during non-working hours $15,869 $768 - - $15,869
-
MMBtu
02 2.4221: Install compressor air intakes in coolest locations $6,834 $18,630 $6,834
122,802
kWh
- -
03 2.7491: Insulate glazing, walls, ceilings, and roofs $4,117 $128,000 - - $4,117
-
MMBtu
04 2.7142: Utilize higher efficiency lamps and/or ballasts $3,838 $30,000 $3,523
63,306
kWh
$315
-
kW-mo/yr
-
05 2.4221: Install compressor air intakes in coolest locations $1,501 $1,630 $1,501
26,964
kWh
- -
06 2.6212: Turn off equipment during breaks, reduce operating time $1,272 - $1,272
22,860
kWh
- -
07 2.6212: Turn off equipment during breaks, reduce operating time $848 - $848
15,240
kWh
- -
TOTAL RECOMMENDED $34,279 $179,028 $13,978
251,172
kWh
$315
-
kW-mo/yr
$19,986
-
MMBtu
TOTAL IMPLEMENTED $30,162 $51,028 $13,978
251,172
kWh
$315
-
kW-mo/yr
$15,869
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs