Assessment Year | 1999 |
---|---|
Principal Product | foam tape, decorative metal laminates, drawer inserts |
NAICS |
n/a
|
SIC | 3471: Electroplating, Plating, Polishing, Anodizing, and Coloring |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
110,000
ft2
|
Annual Production | 5,812
thousand feet
|
Production Hrs. Annual | 4,160
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $101,482 | 1,599,062 |
kWh
|
$0.063 |
Electricity Demand | $33,850 | 6,642 |
kW-mo/yr
|
$5.10 |
Electricity Fees | $13,278 | - |
|
- |
Natural Gas | $108,845 | 17,337 |
MMBtu
|
$6.28 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $74,161 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $4,887 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $65,104 | $361,250 |
$31,564
497,362
kWh
|
$14,680
-
kW-mo/yr
|
$38,860
-
MMBtu
|
$(-20,000.0) | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,147 | $6,075 |
$2,288
36,049
kWh
|
$859
-
kW-mo/yr
|
- | - | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $2,455 | $80 |
$1,786
28,136
kWh
|
$669
-
kW-mo/yr
|
- | - | |
04 | 3.3132: Use reverse osmosis to concentrate material | $1,558 | $5,000 |
$(-112.0)
(-1,758)
kWh
|
- |
$2,405
-
MMBtu
|
$(-735.0) | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $837 | $1,976 |
$837
13,189
kWh
|
- | - | - | |
06 | 2.7124: Make a practice of turning off lights when not needed | $558 | - |
$558
8,792
kWh
|
- | - | - | |
07 | 2.4221: Install compressor air intakes in coolest locations | $316 | $1,425 |
$316
4,982
kWh
|
- | - | - | |
08 | 2.4221: Install compressor air intakes in coolest locations | $186 | $880 |
$186
2,931
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $74,161 | $376,686 |
$37,423
589,683
kWh
|
$16,208
-
kW-mo/yr
|
$41,265
-
MMBtu
|
$(-20,735.0) | ||
TOTAL IMPLEMENTED | $4,887 | $6,505 |
$2,548
40,152
kWh
|
$669
-
kW-mo/yr
|
$2,405
-
MMBtu
|
$(-735.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs