Assessment Year | 1999 |
---|---|
Principal Product | Thick Plastic Parts |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $1 M to 5M |
# of Employees | 48 |
Plant Area |
62,000
ft2
|
Annual Production | 5,265,000
lb
|
Production Hrs. Annual | 6,120
hrs
|
Location (State) | Massachusetts |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $152,372 | 2,526,378 |
kWh
|
$0.060 |
Electricity Demand | $42,251 | 7,425 |
kW-mo/yr
|
$5.69 |
Natural Gas | $2,713 | 198 |
MMBtu
|
$13.70 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $7,242 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,483 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,858 | - |
$1,858
28,722
kWh
|
- | - | |
02 | 2.3212: Optimize plant power factor | $303 | $117 |
$303
4,689
kWh
|
- | - | |
03 | 2.7135: Install occupancy sensors | $322 | $248 |
$322
4,982
kWh
|
- | - | |
04 | 2.4131: Size electric motors for peak operating efficiency | $879 | $4,225 |
$723
11,137
kWh
|
$156
-
kW-mo/yr
|
- | |
05 | 2.4221: Install compressor air intakes in coolest locations | $114 | $470 |
$114
1,758
kWh
|
- | - | |
06 | 4.454: Modify startup/shutdown times | $3,766 | - | - |
$7,463
-
kW-mo/yr
|
$(-3,697.0) | |
TOTAL RECOMMENDED | $7,242 | $5,060 |
$3,320
51,288
kWh
|
$7,619
-
kW-mo/yr
|
$(-3,697.0) | ||
TOTAL IMPLEMENTED | $2,483 | $365 |
$2,483
38,393
kWh
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs