| Assessment Year | 1997 |
|---|---|
| Principal Product | monofilament |
| NAICS |
n/a
|
| SIC | 3089: Plastics Products, Not Elsewhere Classified |
| Sales Range | $10 M to 50M |
| # of Employees | 107 |
| Plant Area |
87,000
ft2
|
| Annual Production | 3,000,000
ton
|
| Production Hrs. Annual | 8,400
hrs
|
| Location (State) | New York |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $594,410 | 9,427,609 |
kWh
|
$0.063 |
| Electricity Demand | $201,096 | 15,102 |
kW-mo/yr
|
$13.32 |
| Natural Gas | $39,698 | 4,466 |
MMBtu
|
$8.89 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $92,084 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $26,371 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $57,769 | $221,193 |
$57,529
910,903
kWh
|
$17,716
-
kW-mo/yr
|
$(-17,476.0)
-
MMBtu
|
|
| 02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $18,467 | $41,542 |
$14,104
223,329
kWh
|
$4,363
-
kW-mo/yr
|
- | |
| 03 | 2.2511: Insulate bare equipment | $7,904 | $4,620 |
$7,904
125,147
kWh
|
- | - | |
| 04 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $4,578 | $19,800 | - |
$7,548
-
kW-mo/yr
|
$(-2,970.0)
-
MMBtu
|
|
| 05 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $2,118 | $5,000 |
$2,610
41,325
kWh
|
$812
-
kW-mo/yr
|
$(-1,304.0)
-
MMBtu
|
|
| 06 | 2.4131: Size electric motors for peak operating efficiency | $970 | $900 |
$740
11,723
kWh
|
$230
-
kW-mo/yr
|
- | |
| 07 | 2.4221: Install compressor air intakes in coolest locations | $278 | - |
$278
4,396
kWh
|
- | - | |
| TOTAL RECOMMENDED | $92,084 | $293,055 |
$83,165
1,316,823
kWh
|
$30,669
-
kW-mo/yr
|
$(-21,750.0)
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $26,371 | $46,162 |
$22,008
348,476
kWh
|
$4,363
-
kW-mo/yr
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs