Assessment Year | 1997 |
---|---|
Principal Product | Printed Fabric |
NAICS |
n/a
|
SIC | 2261: Finishers of Broadwoven Fabrics of Cotton |
Sales Range | $10 M to 50M |
# of Employees | 117 |
Plant Area |
105,000
ft2
|
Annual Production | 150,000,000
thousand feet
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Rhode Island |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $342,176 | 4,481,536 |
kWh
|
$0.076 |
Electricity Demand | $76,866 | 10,760 |
kW-mo/yr
|
$7.14 |
Electricity Fees | $1,583 | - |
|
- |
Natural Gas | $447,494 | 105,965 |
MMBtu
|
$4.22 |
Fuel Oil #6 | $238,744 | 78,573 |
MMBtu
|
$3.04 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $148,850 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $134,501 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Fuel Oil #6 Savings | Other Liquid (haz) Savings | Solid Waste (haz) Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.2449: Recover heat from exhausted steam, hot air or hot water | $95,807 | $47,527 |
$(-2,529.0)
(-33,118)
kWh
|
$(-349.0)
-
kW-mo/yr
|
- |
$98,685
-
MMBtu
|
- | - | |
02 | 2.2414: Use waste heat from hot flue gases to preheat | $5,382 | $1,100 | - | - |
$1,838
-
MMBtu
|
$3,544
-
MMBtu
|
- | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,884 | $4,925 |
$4,118
53,341
kWh
|
$766
-
kW-mo/yr
|
- | - | - | - | |
04 | 3.4145: Use magnetic technology to treat water | $7,561 | $18,983 | - | - | - | - |
$2,000
-
gal
|
$5,561
-
lb
|
|
05 | 2.2437: Recover waste heat from equipment | $1,406 | $858 | - | - |
$1,406
-
MMBtu
|
- | - | - | |
06 | 2.4221: Install compressor air intakes in coolest locations | $604 | $272 |
$604
7,913
kWh
|
- | - | - | - | - | |
07 | 2.2136: Install / repair insulation on steam lines | $1,002 | - | - | - |
$342
-
MMBtu
|
$660
-
MMBtu
|
- | - | |
08 | 2.2427: Use waste heat from hot flue gases to preheat incoming fluids | $32,204 | $55,094 | - | - |
$10,898
-
MMBtu
|
$21,306
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $148,850 | $128,759 |
$2,193
28,136
kWh
|
$417
-
kW-mo/yr
|
$14,484
-
MMBtu
|
$124,195
-
MMBtu
|
$2,000
-
gal
|
$5,561
-
lb
|
||
TOTAL IMPLEMENTED | $134,501 | $107,818 |
$2,193
28,136
kWh
|
$417
-
kW-mo/yr
|
$11,240
-
MMBtu
|
$120,651
-
MMBtu
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Fuel Oil #6 Savings | Other Liquid (haz) Savings | Solid Waste (haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs