Assessment Year | 1996 |
---|---|
Principal Product | electrical wire |
NAICS |
n/a
|
SIC | 3699: Electrical Machinery, Equipment, and Supplies, Not Elsewhere |
Sales Range | $10 M to 50M |
# of Employees | 165 |
Plant Area |
550,000
ft2
|
Annual Production | 385,000
thousand feet
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | New Hampshire |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $471,798 | 4,581,770 |
kWh
|
$0.10 |
Electricity Demand | $69,612 | 10,223 |
kW-mo/yr
|
$6.81 |
Natural Gas | $74,233 | 12,014 |
MMBtu
|
$6.18 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $58,061 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7293: Install dry sprinkler system or other method to reduce heating requirements | $25,870 | $11,700 | - | - |
$25,870
-
MMBtu
|
- | - | |
02 | 2.4239: Eliminate or reduce compressed air usage | $4,515 | $822 |
$4,515
54,220
kWh
|
- | - | - | - | |
03 | 2.4221: Install compressor air intakes in coolest locations | $2,149 | $341 |
$2,149
25,791
kWh
|
- | - | - | - | |
04 | 2.2437: Recover waste heat from equipment | $6,420 | $9,000 | - | - |
$6,420
-
MMBtu
|
- | - | |
05 | 2.4314: Use synthetic lubricant | $1,687 | - |
$1,696
20,223
kWh
|
- | - |
$(-9.0)
-
gal
|
- | |
06 | 2.2136: Install / repair insulation on steam lines | $1,195 | $645 | - | - |
$1,195
-
MMBtu
|
- | - | |
07 | 2.2611: Moderate cooling tower outlet temperature | $2,124 | $5,084 |
$2,124
25,498
kWh
|
- | - | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,954 | $51,942 |
$10,056
120,750
kWh
|
$2,898
-
kW-mo/yr
|
- | - | - | |
09 | 3.4145: Use magnetic technology to treat water | $1,147 | $2,800 | - | - | - | - |
$1,147
-
lb
|
|
TOTAL RECOMMENDED | $58,061 | $82,334 |
$20,540
246,482
kWh
|
$2,898
-
kW-mo/yr
|
$33,485
-
MMBtu
|
$(-9.0)
-
gal
|
$1,147
-
lb
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Other Liquid (non-haz) Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs