| Assessment Year | 1994 |
|---|---|
| Principal Product | coorrugated products |
| NAICS |
n/a
|
| SIC | 2621: Paper Mills |
| Sales Range | $10 M to 50M |
| # of Employees | 125 |
| Plant Area |
171,375
ft2
|
| Annual Production | 0
units
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | Connecticut |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $534,115 | 6,821,512 |
kWh
|
$0.078 |
| Natural Gas | $108,939 | 33,456 |
MMBtu
|
$3.26 |
| Fuel Oil #4 | $82,833 | 23,401 |
MMBtu
|
$3.54 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $73,800 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|
| 01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $35,014 | $102,795 |
$64,794
827,374
kWh
|
$(-29,780.0)
-
MMBtu
|
|
| 02 | 2.6231: Utilize controls to operate equipment only when needed | $4,797 | $4,000 |
$4,797
61,254
kWh
|
- | |
| 03 | 2.6218: Turn off equipment when not in use | $9,593 | $1,526 |
$9,593
122,509
kWh
|
- | |
| 04 | 2.7122: Disconnect ballasts | $8,033 | $411 |
$8,033
102,579
kWh
|
- | |
| 05 | 2.7124: Make a practice of turning off lights when not needed | $1,707 | - |
$1,707
21,688
kWh
|
- | |
| 06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $597 | $525 |
$597
7,620
kWh
|
- | |
| 07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $6,724 | - |
$6,724
85,580
kWh
|
- | |
| 08 | 2.2511: Insulate bare equipment | $4,792 | $1,267 | - |
$4,792
-
MMBtu
|
|
| 09 | 2.2414: Use waste heat from hot flue gases to preheat | $1,660 | $5,030 | - |
$1,660
-
MMBtu
|
|
| 10 | 2.2113: Repair or replace steam traps | $470 | $1,396 | - |
$470
-
MMBtu
|
|
| 11 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $413 | $1,650 |
$413
5,275
kWh
|
- | |
| TOTAL RECOMMENDED | $73,800 | $118,600 |
$96,658
1,233,879
kWh
|
$(-22,858.0)
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs