Assessment Year 1994
Principal Product Product Marking , Coding
NAICS
n/a
SIC 3569: General Industrial Machinery and Equipment, Not Elsewhere
Sales Range $50
M
to 100
M
# of Employees 790
Plant Area 301,400
ft2
Annual Production 0
units
Production Hrs. Annual 4,420
hrs
Location (State) New Hampshire

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $735,275 8,090,270
kWh
Natural Gas $40,340 8,576
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $38,407 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $6,935

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings LPG Savings
01 2.6212: Turn off equipment during breaks, reduce operating time $12,627 - $12,627
138,921
kWh
-
02 2.2437: Recover waste heat from equipment $9,713 $22,395 - $9,713
-
MMBtu
03 2.1311: Replace electrically-operated equipment with fossil fuel equipment $8,732 $20,860 $8,732
-
kWh
-
04 2.4111: Utilize energy-efficient belts and other improved mechanisms $4,154 - $4,154
46,014
kWh
-
05 2.4221: Install compressor air intakes in coolest locations $1,012 $1,062 $1,012
11,137
kWh
-
06 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $939 $100 $939
12,309
kWh
-
07 2.7111: Reduce illumination to minimum necessary levels $503 $300 $503
5,569
kWh
-
08 2.7135: Install occupancy sensors $400 $416 $400
4,396
kWh
-
09 2.4133: Use most efficient type of electric motors $327 $961 $327
3,517
kWh
-
TOTAL RECOMMENDED $38,407 $46,094 $28,694
221,863
kWh
$9,713
-
MMBtu
TOTAL IMPLEMENTED $6,935 $2,423 $6,935
78,546
kWh
-
Yearly Savings* Imp'd Cost* Electricity Usage Savings LPG Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs