Assessment Year | 1992 |
---|---|
Principal Product | VINYL SHEETING AND FILM |
NAICS |
n/a
|
SIC | 2295: Coated Fabrics, Not Rubberized |
Sales Range | $10 M to 50M |
# of Employees | 116 |
Plant Area |
n/a
|
Annual Production | 21,000
thousand feet
|
Production Hrs. Annual | 5,760
hrs
|
Location (State) | Connecticut |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $577,279 | 6,085,580 |
kWh
|
$0.095 |
Natural Gas | $116,960 | 35,302 |
MMBtu
|
$3.31 |
Fuel Oil #6 | $44,541 | 16,624 |
MMBtu
|
$2.68 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $44,383 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $20,358 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | LPG Savings | Fuel Oil #6 Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.1331: Burn a less expensive grade of fuel | $20,512 | - | - |
$34,170
-
MMBtu
|
$(-13,658.0)
-
MMBtu
|
- | |
02 | 2.7316: Centralize control of exhaust fans to ensure their shutdown, or establish program to ensure manual shutdown | $10,171 | $100 |
$10,171
107,268
kWh
|
- | - | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,808 | $6,580 |
$4,808
50,703
kWh
|
- | - | - | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,251 | $5,020 |
$2,251
23,740
kWh
|
- | - | - | |
05 | 2.2122: Install / repair insulation on condensate lines | $1,845 | $600 | - |
$1,263
-
MMBtu
|
- |
$582
-
MMBtu
|
|
06 | 2.2414: Use waste heat from hot flue gases to preheat | $1,480 | $2,854 | - |
$1,014
-
MMBtu
|
- |
$466
-
MMBtu
|
|
07 | 2.2135: Repair and eliminate steam leaks | $1,312 | $300 | - |
$950
-
MMBtu
|
- |
$362
-
MMBtu
|
|
08 | 2.1393: Use steam sparging or injections in place of indirect heating | $742 | $1,668 | - |
$536
-
MMBtu
|
- |
$206
-
MMBtu
|
|
09 | 2.4312: Improve lubrication practices | $750 | - |
$750
7,913
kWh
|
- | - | - | |
10 | 2.4221: Install compressor air intakes in coolest locations | $512 | $77 |
$512
5,275
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $44,383 | $17,199 |
$18,492
194,899
kWh
|
$37,933
-
MMBtu
|
$(-13,658.0)
-
MMBtu
|
$1,616
-
MMBtu
|
||
TOTAL IMPLEMENTED | $20,358 | $12,102 |
$14,979
157,971
kWh
|
$3,763
-
MMBtu
|
- |
$1,616
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | LPG Savings | Fuel Oil #6 Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs