| Assessment Year | 1986 |
|---|---|
| Principal Product | TRACK PINS FOR TANKS |
| NAICS |
n/a
|
| SIC | 3599: Industrial and Commercial Machinery and Equipment, Not Elsewhere Classified |
| Sales Range | $5 M to 10M |
| # of Employees | 75 |
| Plant Area |
n/a
|
| Annual Production | 558,000
pieces
|
| Production Hrs. Annual | 6,864
hrs
|
| Location (State) | Massachusetts |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $187,558 | 2,151,817 |
kWh
|
$0.087 |
| Natural Gas | $14,699 | 2,395 |
MMBtu
|
$6.14 |
| LPG | $11,500 | 824 |
MMBtu
|
$13.96 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $40,073 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $22,617 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
|---|---|---|---|---|---|
| 01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $4,650 | $2,760 |
$4,650
53,341
kWh
|
|
| 02 | 2.5123: Reduce fluid flow rates | $17,169 | $20,900 |
$17,169
196,952
kWh
|
|
| 03 | 2.4133: Use most efficient type of electric motors | $2,530 | $3,500 |
$2,530
29,015
kWh
|
|
| 04 | 2.4221: Install compressor air intakes in coolest locations | $287 | $100 |
$287
3,224
kWh
|
|
| 05 | 2.7111: Reduce illumination to minimum necessary levels | $827 | $240 |
$827
9,379
kWh
|
|
| 06 | 2.2614: Use cooling tower or economizer to replace chiller cooling | $14,610 | $22,000 |
$14,610
167,937
kWh
|
|
| TOTAL RECOMMENDED | $40,073 | $49,500 |
$40,073
459,848
kWh
|
||
| TOTAL IMPLEMENTED | $22,617 | $28,500 |
$22,617
259,672
kWh
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs