Assessment Year | 1985 |
---|---|
Principal Product | NYLON & POLYESTER CLOTH |
NAICS |
n/a
|
SIC | 2241: Narrow Fabric and Other Smallware Mills: Cotton, Wool, Silk, and Manmade Fiber |
Sales Range | $10 M to 50M |
# of Employees | 200 |
Plant Area |
n/a
|
Annual Production | 0
units
|
Production Hrs. Annual | 7,200
hrs
|
Location (State) | Rhode Island |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,201,805 | 14,084,994 |
kWh
|
$0.085 |
Fuel Oil #6 | $183,692 | 35,659 |
MMBtu
|
$5.15 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $34,743 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Fuel Oil #6 Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $1,352 | $550 |
$1,352
15,826
kWh
|
- | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,279 | $476 |
$13,279
154,162
kWh
|
- | - | |
03 | 2.7122: Disconnect ballasts | $2,457 | $1,250 |
$2,457
28,722
kWh
|
- | - | |
04 | 2.7226: Use computer programs to optimize hvac performance | $450 | $1,200 |
$450
5,275
kWh
|
- | - | |
05 | 3.6121: Burn waste paper for heat | $9,651 | $9,075 | - |
$8,151
-
MMBtu
|
$1,500 | |
06 | 2.2443: Re-use or recycle hot or cold process exhaust air | $2,006 | $2,027 |
$2,006
23,447
kWh
|
- | - | |
07 | 2.3191: Use demand controller or load shedder | $5,548 | $15,000 |
$5,548
-
kWh
|
- | - | |
TOTAL RECOMMENDED | $34,743 | $29,578 |
$25,092
227,432
kWh
|
$8,151
-
MMBtu
|
$1,500 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Fuel Oil #6 Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs