| Assessment Year | 2026 |
|---|---|
| Principal Product | Wholesale grocery distribution |
| NAICS | 424490: Other Grocery and Related Products Merchant Wholesalers |
| SIC | 5141: Groceries, General Line |
| Sales Range | greater than $500 M |
| # of Employees | 400 |
| Plant Area |
75,000
ft2
|
| Annual Production | 22,000,000
units
|
| Production Hrs. Annual | 8,760
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,182,591 | 18,117,550 |
kWh
|
$0.065 |
| Electricity Demand | $588,818 | 34,616 |
kW-mo/yr
|
$17.01 |
| Electricity Fees | $208,265 | - |
|
- |
| TOTAL YEARLY COSTS | $1,979,674 | |||
| RECOMMENDED SAVINGS* | $644,231 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.2621: Modify refrigeration system to operate at a lower pressure | $59,468 | $219,165 |
$59,468
910,696
kWh
|
- | |
| 02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,180 | - |
$1,180
18,058
kWh
|
- | |
| 03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,744 | $7,812 |
$2,068
31,667
kWh
|
$1,677
-
kW-mo/yr
|
|
| 04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $23,347 | $8,904 |
$10,432
159,758
kWh
|
$12,915
-
kW-mo/yr
|
|
| 05 | 2.9114: Use solar heat to make electricty | $556,491 | $7,323,896 |
$497,039
7,611,629
kWh
|
$59,452
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $644,231 | $7,559,777 |
$570,188
8,731,808
kWh
|
$74,043
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | - | - | - | - | ||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs