Assessment Year | 2023 |
---|---|
Principal Product | Perishable Prepared Food |
NAICS | 311991: Perishable Prepared Food Manufacturing |
SIC | 2099: Food Preparations, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 400 |
Plant Area |
720,000
ft2
|
Annual Production | 64,800,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,613,861 | 18,970,350 |
kWh
|
$0.085 |
Electricity Demand | $501,595 | 34,833 |
kW-mo/yr
|
$14.40 |
Electricity Fees | $79,973 | - |
|
- |
LPG | $19,726 | 727 |
MMBtu
|
$27.13 |
TOTAL YEARLY COSTS | $2,215,155 | |||
RECOMMENDED SAVINGS* | $287,021 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
---|---|---|---|---|---|---|---|
01 | 2.2621: Modify refrigeration system to operate at a lower pressure | $98,547 | $220,400 |
$79,985
941,000
kWh
|
$18,562
-
kW-mo/yr
|
- | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $20,015 | $37,491 |
$16,242
191,081
kWh
|
$3,773
-
kW-mo/yr
|
- | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,033 | $14,614 |
$5,133
60,384
kWh
|
$1,901
-
kW-mo/yr
|
- | |
04 | 2.7442: Keep doors and windows shut when not on use | $96,000 | - |
$77,914
916,634
kWh
|
$18,086
-
kW-mo/yr
|
- | |
05 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $24,164 | - |
$19,614
230,751
kWh
|
$4,550
-
kW-mo/yr
|
- | |
06 | 2.1321: Replace fossil fuel equipment with electrical equipment | $22,998 | $53,560 |
$2,653
31,207
kWh
|
$619
-
kW-mo/yr
|
$19,726
-
MMBtu
|
|
07 | 2.7232: Replace existing hvac unit with high efficiency model | $18,264 | $99,888 |
$9,120
107,289
kWh
|
$9,144
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $287,021 | $425,953 |
$210,659
2,478,346
kWh
|
$56,635
-
kW-mo/yr
|
$19,726
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs