Assessment Year | 2022 |
---|---|
Principal Product | paper processing fabrics |
NAICS | 332618: Other Fabricated Wire Product Manufacturing |
SIC | 3496: Miscellaneous Fabricated Wire Products |
Sales Range | $50 M to 100M |
# of Employees | 60 |
Plant Area |
128,000
ft2
|
Annual Production | 70,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $441,233 | 4,085,496 |
kWh
|
$0.11 | |
Electricity Demand | $124,969 | 11,148 |
kW-mo/yr
|
$11.21 | |
LPG | $713 | 22 |
MMBtu
|
$32.60 | |
Waste Disposal Costs | |||||
Water Usage | $750 | 15 |
Tgal
|
$50.00 | |
Water Disposal | $750 | 15 |
Tgal
|
$50.00 | |
TOTAL YEARLY COSTS | $568,415 | ||||
RECOMMENDED SAVINGS* | $42,303 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | LPG Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|---|
01 | 2.8114: Change rate schedules or other changes in utility service | $673 | - | - | - | $673 | - | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $21,493 | $30,000 |
$21,493
199,009
kWh
|
- | - | - | - | - | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $5,079 | - |
$5,079
47,050
kWh
|
- | - | - | - | - | |
04 | 2.1321: Replace fossil fuel equipment with electrical equipment | $808 | $29,000 |
$(-59.2)
(-549)
kWh
|
- | - |
$712
-
MMBtu
|
- | $155 | |
05 | 2.4224: Upgrade controls on compressors | $10,089 | - | - |
$10,089
-
kW-mo/yr
|
- | - | - | - | |
06 | 2.7221: Lower temperature during the winter season and vice-versa | $3,938 | - |
$4,118
38,126
kWh
|
- | - | - | $(-180.0) | - | |
07 | 2.7224: Reduce space conditioning during non-working hours | $223 | $180 |
$403
3,734
kWh
|
- | - | - | $(-180.0) | - | |
TOTAL RECOMMENDED | $42,303 | $59,180 |
$31,033
287,370
kWh
|
$10,089
-
kW-mo/yr
|
$673 |
$712
-
MMBtu
|
$(-360.0) | $155 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | LPG Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs