Assessment Year | 2022 |
---|---|
Principal Product | Fabricated Structural Steel |
NAICS | 332312: Fabricated Structural Metal Manufacturing |
SIC | 3441: Fabricated Structural Metal |
Sales Range | $50 M to 100M |
# of Employees | 260 |
Plant Area |
289,000
ft2
|
Annual Production | 5,000,000
lb
|
Production Hrs. Annual | 7,300
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $322,334 | 5,083,282 |
kWh
|
$0.063 |
Electricity Demand | $256,470 | 19,056 |
kW-mo/yr
|
$13.46 |
TOTAL YEARLY COSTS | $578,804 | |||
RECOMMENDED SAVINGS* | $8,968 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $5,531 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,079 | $50 |
$2,079
32,788
kWh
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,436 | $360 |
$2,436
38,410
kWh
|
- | |
03 | 2.7261: Install timers and/or thermostats | $561 | $100 |
$561
8,845
kWh
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,897 | $1,010 |
$1,972
31,105
kWh
|
$925
-
kW-mo/yr
|
|
05 | 2.7134: Use photocell controls | $797 | $703 |
$797
12,568
kWh
|
- | |
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $198 | $338 |
$198
3,132
kWh
|
- | |
TOTAL RECOMMENDED | $8,968 | $2,561 |
$8,043
126,848
kWh
|
$925
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $5,531 | $1,708 |
$4,606
72,647
kWh
|
$925
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs