Assessment Year | 2022 |
---|---|
Principal Product | Metal Fabrication |
NAICS | 332312: Fabricated Structural Metal Manufacturing |
SIC | 3441: Fabricated Structural Metal |
Sales Range | less than $500 k |
# of Employees | 200 |
Plant Area |
35,000
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 2,496
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $783,598 | 7,363,048 |
kWh
|
$0.11 | |
Electricity Demand | $4,103 | 1,000 |
kW-mo/yr
|
$4.10 | |
Natural Gas | $19,591 | 3,511 |
MMBtu
|
$5.58 | |
Waste Disposal Costs | |||||
Water Usage | $52,934 | 10,410 |
Tgal
|
$5.08 | |
TOTAL YEARLY COSTS | $860,226 | ||||
RECOMMENDED SAVINGS* | $118,919 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $6,914 | $63 |
$6,914
64,969
kWh
|
- | - | |
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $7,397 | $100 |
$7,397
69,506
kWh
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $10,320 | $900 |
$10,320
96,972
kWh
|
- | - | |
04 | 2.7134: Use photocell controls | $2,098 | $555 |
$2,098
19,710
kWh
|
- | - | |
05 | 2.7135: Install occupancy sensors | $448 | $200 |
$448
4,210
kWh
|
- | - | |
06 | 2.7124: Make a practice of turning off lights when not needed | $478 | $300 |
$478
4,492
kWh
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,379 | $6,434 |
$5,379
50,548
kWh
|
$1,000
-
kW-mo/yr
|
- | |
08 | 2.4322: Use or replace with energy efficient substitutes | $25,733 | $189,000 |
$25,733
241,795
kWh
|
- | - | |
09 | 2.3212: Optimize plant power factor | $12,415 | $106,570 | - | - | $12,415 | |
10 | 2.9114: Use solar heat to make electricty | $46,737 | $646,020 |
$46,737
439,165
kWh
|
- | - | |
TOTAL RECOMMENDED | $118,919 | $950,142 |
$105,504
991,367
kWh
|
$1,000
-
kW-mo/yr
|
$12,415 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs