| Assessment Year | 2022 |
|---|---|
| Principal Product | High School |
| NAICS | 611110: Elementary and Secondary Schools |
| SIC | 8211: Elementary and Secondary Schools |
| Sales Range | less than $500 k |
| # of Employees | 100 |
| Plant Area |
130,000
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 2,665
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $260,714 | 2,782,702 |
kWh
|
$0.094 |
| Electricity Demand | $31,456 | 7,555 |
kW-mo/yr
|
$4.16 |
| TOTAL YEARLY COSTS | $292,170 | |||
| RECOMMENDED SAVINGS* | $25,111 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $19,618 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7261: Install timers and/or thermostats | $2,827 | $100 |
$2,827
31,410
kWh
|
- | |
| 02 | 2.7135: Install occupancy sensors | $747 | $375 |
$747
7,949
kWh
|
- | |
| 03 | 4.662: Level one – add communication using iiot devices to existing control system to modify operations | $5,493 | $3,200 |
$5,493
58,437
kWh
|
- | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $16,044 | $31,514 |
$12,875
136,971
kWh
|
$3,169
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $25,111 | $35,189 |
$21,942
234,767
kWh
|
$3,169
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $19,618 | $31,989 |
$16,449
176,330
kWh
|
$3,169
-
kW-mo/yr
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs