Assessment Year | 2023 |
---|---|
Principal Product | Middle School |
NAICS | 611110: Elementary and Secondary Schools |
SIC | 8211: Elementary and Secondary Schools |
Sales Range | less than $500 k |
# of Employees | 68 |
Plant Area |
60,000
ft2
|
Annual Production | 1
units
|
Production Hrs. Annual | 1,950
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $234,487 | 2,757,929 |
kWh
|
$0.085 |
Electricity Demand | $35,402 | 8,588 |
kW-mo/yr
|
$4.12 |
TOTAL YEARLY COSTS | $269,889 | |||
RECOMMENDED SAVINGS* | $40,177 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $36,380 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $19,862 | $3,500 |
$19,862
233,673
kWh
|
- | |
02 | 2.7423: Reduce heat gain by window tinting | $2,652 | $1,133 |
$2,652
31,200
kWh
|
- | |
03 | 2.7135: Install occupancy sensors | $3,644 | $1,700 |
$3,644
42,869
kWh
|
- | |
04 | 2.7211: Clean and maintain refrigerant condensers and towers | $1,145 | $788 |
$1,145
13,472
kWh
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $12,874 | $16,460 |
$10,586
124,542
kWh
|
$2,288
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $40,177 | $23,581 |
$37,889
445,756
kWh
|
$2,288
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $36,380 | $21,660 |
$34,092
401,084
kWh
|
$2,288
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs