| Assessment Year | 2024 |
|---|---|
| Principal Product | Office Building |
| NAICS | 921110: Executive Offices |
| SIC | 1542: General Contractors-Nonresidential Buildings, Other than Industrial Buildings and Warehouses |
| Sales Range | less than $500 k |
| # of Employees | 200 |
| Plant Area |
75,000
ft2
|
| Annual Production | 1
units
|
| Production Hrs. Annual | 1,664
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $222,628 | 2,536,000 |
kWh
|
$0.088 |
| Electricity Demand | $21,413 | 4,485 |
kW-mo/yr
|
$4.77 |
| TOTAL YEARLY COSTS | $244,041 | |||
| RECOMMENDED SAVINGS* | $47,781 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $44,863 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.7211: Clean and maintain refrigerant condensers and towers | $9,288 | - |
$9,288
105,545
kWh
|
- | |
| 02 | 2.7261: Install timers and/or thermostats | $26,997 | $750 |
$26,997
306,784
kWh
|
- | |
| 03 | 2.7425: Clean or color roof to reduce solar load | $1,836 | $4,158 |
$1,836
20,864
kWh
|
- | |
| 04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $8,578 | $20,143 |
$6,167
70,082
kWh
|
$2,411
-
kW-mo/yr
|
|
| 05 | 2.4133: Use most efficient type of electric motors | $1,082 | $3,400 |
$1,082
12,300
kWh
|
- | |
| TOTAL RECOMMENDED | $47,781 | $28,451 |
$45,370
515,575
kWh
|
$2,411
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $44,863 | $20,893 |
$42,452
482,411
kWh
|
$2,411
-
kW-mo/yr
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs