Assessment Year | 2017 |
---|---|
Principal Product | Amines |
NAICS | 325998: All Other Miscellaneous Chemical Product and Preparation Manufacturing |
SIC | 2869: Industrial Organic Chemicals, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 107 |
Plant Area |
2,861,032
ft2
|
Annual Production | 285,000,000
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,390,190 | 31,867,600 |
kWh
|
$0.044 |
Electricity Demand | $432,228 | 56,208 |
kW-mo/yr
|
$7.69 |
Natural Gas | $2,486,844 | 746,800 |
MMBtu
|
$3.33 |
TOTAL YEARLY COSTS | $4,309,262 | |||
RECOMMENDED SAVINGS* | $256,975 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $46,204 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $69,401 | $106,209 | - | - | $69,401 | - | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $25,903 | $21,300 |
$25,903
637,858
kWh
|
- | - | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,795 | $4,000 |
$4,795
118,075
kWh
|
- | - | - | |
04 | 2.6218: Turn off equipment when not in use | $7,832 | $100 | - | - | - |
$7,832
-
MMBtu
|
|
05 | 2.1223: Install smaller boiler (increase high fire duty cycle) | $134,326 | $621,739 | - | - | - |
$134,326
-
MMBtu
|
|
06 | 2.7425: Clean or color roof to reduce solar load | $7,044 | $34,056 |
$7,044
176,090
kWh
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,997 | $3,280 |
$5,635
140,883
kWh
|
$1,362
-
kW-mo/yr
|
- | - | |
08 | 2.7261: Install timers and/or thermostats | $330 | $400 |
$330
8,238
kWh
|
- | - | - | |
09 | 2.7135: Install occupancy sensors | $347 | $585 |
$347
8,665
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $256,975 | $791,669 |
$44,054
1,089,809
kWh
|
$1,362
-
kW-mo/yr
|
$69,401 |
$142,158
-
MMBtu
|
||
TOTAL IMPLEMENTED | $46,204 | $29,665 |
$37,010
913,719
kWh
|
$1,362
-
kW-mo/yr
|
- |
$7,832
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs