Assessment Year | 2003 |
---|---|
Principal Product | fasteners |
NAICS | 336413: Other Aircraft Parts and Auxiliary Equipment Manufacturing |
SIC | 3728: Aircraft Parts and Auxiliary Equipment, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 250 |
Plant Area |
130,000
ft2
|
Annual Production | 7,500,000
pieces
|
Production Hrs. Annual | 7,200
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $373,083 | 3,307,328 |
kWh
|
$0.11 |
Electricity Demand | $118,723 | 9,180 |
kW-mo/yr
|
$12.93 |
Electricity Fees | $4,840 | - |
|
- |
Natural Gas | $31,914 | 6,657 |
MMBtu
|
$4.79 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $19,711 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $17,239 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $2,854 | $1,545 |
$2,386
21,185
kWh
|
$468
-
kW-mo/yr
|
- | - | |
02 | 2.7124: Make a practice of turning off lights when not needed | $5,770 | - |
$3,235
28,669
kWh
|
$2,535
-
kW-mo/yr
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,079 | $410 |
$1,232
10,957
kWh
|
$367
-
kW-mo/yr
|
- | $(-520.0) | |
04 | 2.4221: Install compressor air intakes in coolest locations | $3,410 | $1,000 |
$2,852
25,303
kWh
|
$558
-
kW-mo/yr
|
- | - | |
05 | 2.4239: Eliminate or reduce compressed air usage | $346 | - |
$289
2,563
kWh
|
$57
-
kW-mo/yr
|
- | - | |
06 | 2.2514: Cover open tanks | $3,464 | $420 |
$2,896
25,695
kWh
|
$568
-
kW-mo/yr
|
- | - | |
07 | 2.2414: Use waste heat from hot flue gases to preheat | $2,472 | $4,000 | - | - |
$2,472
-
MMBtu
|
- | |
08 | 2.6221: Use most efficient equipment at it's maximum capacity and less efficient equipment only when necessary | $316 | $400 |
$264
2,339
kWh
|
$52
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $19,711 | $7,775 |
$13,154
116,711
kWh
|
$4,605
-
kW-mo/yr
|
$2,472
-
MMBtu
|
$(-520.0) | ||
TOTAL IMPLEMENTED | $17,239 | $3,775 |
$13,154
116,711
kWh
|
$4,605
-
kW-mo/yr
|
- | $(-520.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs