Assessment Year | 2001 |
---|---|
Principal Product | aerospace metal ducts |
NAICS |
n/a
|
SIC | 3728: Aircraft Parts and Auxiliary Equipment, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 300 |
Plant Area |
125,000
ft2
|
Annual Production | 163,285
pieces
|
Production Hrs. Annual | 5,246
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $127,553 | 2,498,389 |
kWh
|
$0.051 |
Electricity Demand | $97,945 | 18,780 |
kW-mo/yr
|
$5.22 |
Electricity Fees | $99,769 | - |
|
- |
Natural Gas | $67,862 | 8,427 |
MMBtu
|
$8.05 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $143,637 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $112,781 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Personnel Changes Savings | Administrative Changes Savings | Primary Product Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,734 | $100 |
$2,093
18,472
kWh
|
$421
-
kW-mo/yr
|
$(-780.0) | - | - | |
02 | 2.4221: Install compressor air intakes in coolest locations | $2,848 | $164 |
$2,371
20,931
kWh
|
$477
-
kW-mo/yr
|
- | - | - | |
03 | 2.3134: Shift from daytime to nighttime operation | $54,047 | $450 |
$26,813
235,000
kWh
|
$60,984
-
kW-mo/yr
|
$(-33,750.0) | - | - | |
04 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $28,008 | $15,300 | - | - | - | $28,008 | - | |
05 | 4.611: Begin a practice of predictive / preventative maintenance | $57,000 | $102,000 | - | - | $(-78,000.0) | - | $135,000 | |
TOTAL RECOMMENDED | $143,637 | $118,014 |
$31,277
274,403
kWh
|
$61,882
-
kW-mo/yr
|
$(-112,530.0) | $28,008 | $135,000 | ||
TOTAL IMPLEMENTED | $112,781 | $102,550 |
$28,906
253,472
kWh
|
$61,405
-
kW-mo/yr
|
$(-112,530.0) | - | $135,000 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs