Assessment Year 2006
Principal Product Catfish
NAICS 311710: Seafood Product Preparation and Packaging
SIC 2092: Prepared Fresh or Frozen Fish and Seafoods
Sales Range $10
M
to 50
M
# of Employees 160
Plant Area 80,000
ft2
Annual Production 28,000,000
lb
Production Hrs. Annual 3,120
hrs
Location (State) Louisiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $284,075 3,286,408
kWh
Electricity Demand $32,305 7,841
kW-mo/yr
Electricity Fees $11,386 -
Natural Gas $11,896 870
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $70,380 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $45,426

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Personnel Changes Savings
01 2.2511: Insulate bare equipment $44,247 $9,812 $40,085
463,717
kWh
$2,624
-
kW-mo/yr
$1,538 - -
02 2.4222: Install adequate dryers on air lines to eliminate blowdown $11,560 $152 $11,158
129,089
kWh
- $402 - -
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $4,564 $6,011 $4,405
50,958
kWh
- $159 - -
04 2.2511: Insulate bare equipment $1,179 $317 $1,068
12,363
kWh
$70
-
kW-mo/yr
$41 - -
05 2.2511: Insulate bare equipment $1,041 $5,661 $943
10,907
kWh
$62
-
kW-mo/yr
$36 - -
06 2.7135: Install occupancy sensors $328 $240 $317
3,667
kWh
- $11 - -
07 2.7134: Use photocell controls $320 $90 $309
3,571
kWh
- $11 - -
08 2.7142: Utilize higher efficiency lamps and/or ballasts $666 $385 $300
3,469
kWh
$20
-
kW-mo/yr
$12 - $334
09 2.2511: Insulate bare equipment $274 $129 - - - $274
-
MMBtu
-
10 4.611: Begin a practice of predictive / preventative maintenance $6,201 $382 $773
8,942
kWh
- $28 - $5,400
TOTAL RECOMMENDED $70,380 $23,179 $59,358
686,683
kWh
$2,776
-
kW-mo/yr
$2,238 $274
-
MMBtu
$5,734
TOTAL IMPLEMENTED $45,426 $10,129 $41,153
476,080
kWh
$2,694
-
kW-mo/yr
$1,579 - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Natural Gas Savings Personnel Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs