| Assessment Year | 2005 |
|---|---|
| Principal Product | Farm equipment |
| NAICS | 333111: Farm Machinery and Equipment Manufacturing |
| SIC | 3523: Farm Machinery and Equipment |
| Sales Range | $100 M to 500M |
| # of Employees | 500 |
| Plant Area |
701,000
ft2
|
| Annual Production | 2,303
pieces
|
| Production Hrs. Annual | 5,200
hrs
|
| Location (State) | Louisiana |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $703,827 | 6,426,095 |
kWh
|
$0.11 |
| Electricity Demand | $6,028 | 24,123 |
kW-mo/yr
|
$0.25 |
| Electricity Fees | $25,884 | - |
|
- |
| Other Gas | $44,224 | 3,724 |
MMBtu
|
$11.88 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $440,996 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $322,670 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Fees Savings | Other Gas Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings |
|---|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.7111: Reduce illumination to minimum necessary levels | $79,796 | $4,000 |
$77,023
1,031,609
kWh
|
$2,773 | - | - | - | - | |
| 02 | 2.7134: Use photocell controls | $55,019 | - |
$53,107
711,224
kWh
|
$1,912 | - | - | - | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $47,819 | $22,000 |
$47,819
618,143
kWh
|
- | - | - | - | - | |
| 04 | 2.7224: Reduce space conditioning during non-working hours | $19,616 | - |
$18,934
253,565
kWh
|
$682 | - | - | - | - | |
| 05 | 2.4239: Eliminate or reduce compressed air usage | $16,509 | - |
$15,935
213,402
kWh
|
$574 | - | - | - | - | |
| 06 | 2.7261: Install timers and/or thermostats | $14,813 | - | - | - |
$14,813
-
MMBtu
|
- | - | - | |
| 07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $7,945 | - |
$7,662
105,286
kWh
|
$283 | - | - | - | - | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,872 | - |
$1,715
22,969
kWh
|
$62 | - | - | $2,095 | - | |
| 09 | 2.7134: Use photocell controls | $870 | - |
$840
11,256
kWh
|
$30 | - | - | - | - | |
| 10 | 3.5217: Reuse / recycle/ sell paper products | $7,627 | - | - | - | - |
$7,627
-
lb
|
- | - | |
| 11 | 4.611: Begin a practice of predictive / preventative maintenance | $106,500 | $20,000 | - | - | - | - | $104,000 | $2,500 | |
| 12 | 4.611: Begin a practice of predictive / preventative maintenance | $80,610 | $20,000 | - | - | - | - | $80,610 | - | |
| TOTAL RECOMMENDED | $440,996 | $66,000 |
$223,035
2,967,454
kWh
|
$6,316 |
$14,813
-
MMBtu
|
$7,627
-
lb
|
$186,705 | $2,500 | ||
| TOTAL IMPLEMENTED | $322,670 | $66,000 |
$132,504
1,755,038
kWh
|
$3,056 | - | - | $184,610 | $2,500 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Fees Savings | Other Gas Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | One-time Revenue or Avoided Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs