Assessment Year 2004
Principal Product Plastic agricultural film
NAICS 326113: Unlaminated Plastics Film and Sheet (except Packaging) Manufacturing
SIC 3081: Unsupported Plastics Film and Sheet
Sales Range $10
M
to 50
M
# of Employees 25
Plant Area 150,000
ft2
Annual Production 50,000,000
lb
Production Hrs. Annual 8,568
hrs
Location (State) Louisiana

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $761,772 17,523,200
kWh
Electricity Demand $207,104 28,260
kW-mo/yr
Electricity Fees $118,780 -
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $28,082 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $17,894

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Personnel Changes Savings
01 2.7261: Install timers and/or thermostats $10,188 $1,430 $9,072
208,845
kWh
- $1,116 -
02 2.7111: Reduce illumination to minimum necessary levels $8,957 $570 $6,449
148,466
kWh
$1,527
-
kW-mo/yr
$981 -
03 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $6,000 $2,360 $5,343
122,996
kWh
- $657 -
04 2.7142: Utilize higher efficiency lamps and/or ballasts $1,025 $770 $318
7,323
kWh
- $39 $668
05 2.7134: Use photocell controls $729 $60 $649
14,942
kWh
- $80 -
06 2.7134: Use photocell controls $419 $180 $373
8,592
kWh
- $46 -
07 4.611: Begin a practice of predictive / preventative maintenance $764 $158 - - - $764
TOTAL RECOMMENDED $28,082 $5,528 $22,204
511,164
kWh
$1,527
-
kW-mo/yr
$2,919 $1,432
TOTAL IMPLEMENTED $17,894 $4,098 $13,132
302,319
kWh
$1,527
-
kW-mo/yr
$1,803 $1,432
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Electricity Fees Savings Personnel Changes Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs