Assessment Year | 2002 |
---|---|
Principal Product | Oil field tools |
NAICS |
n/a
|
SIC | 3498: Fabricated Pipe and Pipe Fittings |
Sales Range | $10 M to 50M |
# of Employees | 120 |
Plant Area |
85,690
ft2
|
Annual Production | 207,284
pieces
|
Production Hrs. Annual | 3,840
hrs
|
Location (State) | Louisiana |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $143,677 | 2,495,365 |
kWh
|
$0.058 |
Electricity Demand | $39,700 | 7,307 |
kW-mo/yr
|
$5.43 |
Electricity Fees | $9,401 | - |
|
- |
Natural Gas | $46,301 | 5,173 |
MMBtu
|
$8.95 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $17,175 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $2,243 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.3212: Optimize plant power factor | $12,791 | $19,845 | - |
$12,299
-
kW-mo/yr
|
$492 | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,175 | $525 |
$1,130
19,975
kWh
|
- | $45 | - | |
03 | 2.7111: Reduce illumination to minimum necessary levels | $1,129 | - |
$619
10,944
kWh
|
$467
-
kW-mo/yr
|
$43 | - | |
04 | 2.7135: Install occupancy sensors | $904 | $520 |
$668
11,804
kWh
|
$201
-
kW-mo/yr
|
$35 | - | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $772 | $345 |
$742
13,113
kWh
|
- | $30 | - | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $296 | $120 |
$285
5,039
kWh
|
- | $11 | - | |
07 | 2.8114: Change rate schedules or other changes in utility service | $108 | - | - | - | - | $108 | |
TOTAL RECOMMENDED | $17,175 | $21,355 |
$3,444
60,875
kWh
|
$12,967
-
kW-mo/yr
|
$656 | $108 | ||
TOTAL IMPLEMENTED | $2,243 | $990 |
$2,157
38,127
kWh
|
- | $86 | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs