ITAC Assessment: LE0611
ITAC logo
ITAC Assessment: LE0611
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2026
Principal Product Plastic Component
NAICS 326199: All Other Plastics Product Manufacturing
SIC 3089: Plastics Products, Not Elsewhere Classified
Sales Range $50
M
to 100
M
# of Employees 793
Plant Area 144,639
ft2
Annual Production 900
units
Production Hrs. Annual 8,736
hrs
Location (State) New Jersey

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,763,417 21,229,644
kWh
Electricity Demand $24,183 36,102
kW-mo/yr
Electricity Fees $228,526 -
LPG $17,654 756
MMBtu
Waste Disposal Costs
Water Usage $21,845 4,425
Tgal
Water Disposal $31,981 4,384
Tgal
TOTAL YEARLY COSTS $2,087,606
RECOMMENDED SAVINGS* $144,196 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings LPG Savings
01 2.7261: Install timers and/or thermostats $5,549 - $1,626
19,595
kWh
- $3,923
-
MMBtu
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $13,022 $2,360 $12,879
155,167
kWh
$143
-
kW-mo/yr
-
03 2.7135: Install occupancy sensors $6,024 $2,100 $6,024
72,576
kWh
- -
04 2.7135: Install occupancy sensors $924 $350 $924
11,138
kWh
- -
05 2.7142: Utilize higher efficiency lamps and/or ballasts $38,387 $21,560 $37,966
457,416
kWh
$421
-
kW-mo/yr
-
06 2.4221: Install compressor air intakes in coolest locations $6,159 $4,000 $6,091
73,382
kWh
$68
-
kW-mo/yr
-
07 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $24,193 $16,755 $23,928
288,288
kWh
$265
-
kW-mo/yr
-
08 2.4227: Use compressor air filters $21,640 $40,000 $21,481
258,805
kWh
$159
-
kW-mo/yr
-
09 2.7232: Replace existing hvac unit with high efficiency model $21,077 $86,163 $20,846
251,160
kWh
$231
-
kW-mo/yr
-
10 2.7425: Clean or color roof to reduce solar load $7,221 $34,509 $4,624
55,712
kWh
$2,597
-
kW-mo/yr
-
TOTAL RECOMMENDED $144,196 $207,797 $136,389
1,643,239
kWh
$3,884
-
kW-mo/yr
$3,923
-
MMBtu
TOTAL IMPLEMENTED - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings LPG Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs