Assessment Year | 2024 |
---|---|
Principal Product | Chemical mixing |
NAICS | 424690: Other Chemical and Allied Products Merchant Wholesalers |
SIC | 5169: Chemicals and Allied Products, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 238 |
Plant Area |
270,000
ft2
|
Annual Production | 88,504
ton
|
Production Hrs. Annual | 3,822
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $109,916 | 1,903,767 |
kWh
|
$0.058 |
Electricity Demand | $20,701 | 4,044 |
kW-mo/yr
|
$5.12 |
Electricity Fees | $28,181 | - |
|
- |
Natural Gas | $74,821 | 13,851 |
MMBtu
|
$5.40 |
TOTAL YEARLY COSTS | $233,619 | |||
RECOMMENDED SAVINGS* | $205,517 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $27,784 | - |
$784
13,529
kWh
|
- |
$27,000
-
MMBtu
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $17,317 | $2,200 |
$14,842
255,896
kWh
|
$2,475
-
kW-mo/yr
|
- | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,395 | $660 |
$1,194
20,592
kWh
|
$201
-
kW-mo/yr
|
- | - | - | |
04 | 2.2122: Install / repair insulation on condensate lines | $11,387 | $25,000 | - | - |
$6,005
-
MMBtu
|
$5,382
-
Tgal
|
- | |
05 | 2.4239: Eliminate or reduce compressed air usage | $11,641 | $25,639 |
$11,229
193,610
kWh
|
$412
-
kW-mo/yr
|
- | - | - | |
06 | 2.9112: Use solar heat to heat water | $132,239 | $658,000 |
$48,474
598,450
kWh
|
- | - | - | $83,765 | |
07 | 2.7232: Replace existing hvac unit with high efficiency model | $3,754 | $33,002 |
$3,468
59,976
kWh
|
$286
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $205,517 | $744,501 |
$79,991
1,142,053
kWh
|
$3,374
-
kW-mo/yr
|
$33,005
-
MMBtu
|
$5,382
-
Tgal
|
$83,765 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs