Assessment Year | 2024 |
---|---|
Principal Product | Polished Motor Veichles Parts |
NAICS | 332813: Electroplating, Plating, Polishing, Anodizing, and Coloring |
SIC | 3471: Electroplating, Plating, Polishing, Anodizing, and Coloring |
Sales Range | $500 k to 1M |
# of Employees | 29 |
Plant Area |
66,000
ft2
|
Annual Production | 3,744
units
|
Production Hrs. Annual | 6,110
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $54,932 | 950,114 |
kWh
|
$0.058 |
Electricity Demand | $19,627 | 3,841 |
kW-mo/yr
|
$5.11 |
Electricity Fees | $3,303 | - |
|
- |
Natural Gas | $100,782 | 19,711 |
MMBtu
|
$5.11 |
TOTAL YEARLY COSTS | $178,644 | |||
RECOMMENDED SAVINGS* | $28,113 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.7224: Reduce space conditioning during non-working hours | $812 | - |
$807
13,911
kWh
|
- |
$5
-
MMBtu
|
|
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,039 | - |
$927
15,987
kWh
|
$112
-
kW-mo/yr
|
- | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,562 | $4,791 |
$3,642
62,790
kWh
|
$920
-
kW-mo/yr
|
- | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,224 | $13,206 |
$9,120
157,248
kWh
|
$1,104
-
kW-mo/yr
|
- | |
05 | 2.4221: Install compressor air intakes in coolest locations | $1,754 | $4,000 |
$1,672
28,829
kWh
|
$82
-
kW-mo/yr
|
- | |
06 | 2.7232: Replace existing hvac unit with high efficiency model | $9,722 | $48,010 |
$9,272
159,869
kWh
|
$450
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $28,113 | $70,007 |
$25,440
438,634
kWh
|
$2,668
-
kW-mo/yr
|
$5
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs