Assessment Year | 2023 |
---|---|
Principal Product | Flexible Packaging |
NAICS | 322220: Paper Bag and Coated and Treated Paper Manufacturing |
SIC | 2671: Packaging Paper and Plastics Film, Coated and Laminated |
Sales Range | $50 M to 100M |
# of Employees | 120 |
Plant Area |
210,000
ft2
|
Annual Production | 10,000
units
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $431,294 | 8,267,693 |
kWh
|
$0.052 |
Electricity Demand | $92,750 | 14,512 |
kW-mo/yr
|
$6.39 |
Electricity Fees | $43,799 | - |
|
- |
Natural Gas | $158,992 | 22,049 |
MMBtu
|
$7.21 |
TOTAL YEARLY COSTS | $726,835 | |||
RECOMMENDED SAVINGS* | $48,964 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $6,699 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4221: Install compressor air intakes in coolest locations | $3,677 | $3,000 |
$3,121
60,011
kWh
|
$556
-
kW-mo/yr
|
|
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $26,690 | $37,053 |
$22,843
439,294
kWh
|
$3,847
-
kW-mo/yr
|
|
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,207 | $1,900 |
$1,181
22,714
kWh
|
$26
-
kW-mo/yr
|
|
04 | 2.3212: Optimize plant power factor | $5,492 | $12,810 | - |
$5,492
-
kW-mo/yr
|
|
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,898 | $60,000 |
$11,054
212,576
kWh
|
$844
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $48,964 | $114,763 |
$38,199
734,595
kWh
|
$10,765
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $6,699 | $14,710 |
$1,181
22,714
kWh
|
$5,518
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs