Assessment Year | 2022 |
---|---|
Principal Product | Choclate |
NAICS | 311352: Confectionery Manufacturing from Purchased Chocolate |
SIC | 2064: Candy and Other Confectionery Products |
Sales Range | $10 M to 50M |
# of Employees | 135 |
Plant Area |
120,000
ft2
|
Annual Production | 3,200,000
lb
|
Production Hrs. Annual | 5,434
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $264,424 | 4,050,900 |
kWh
|
$0.065 |
Electricity Demand | $24,795 | 9,736 |
kW-mo/yr
|
$2.55 |
Electricity Fees | $9,282 | - |
|
- |
Natural Gas | $188,378 | 25,140 |
MMBtu
|
$7.49 |
TOTAL YEARLY COSTS | $486,879 | |||
RECOMMENDED SAVINGS* | $107,767 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.8123: Pay utility bills on time | $1,087 | - | - | - | $1,087 | - | - | |
02 | 2.7261: Install timers and/or thermostats | $1,119 | $460 |
$1,119
17,215
kWh
|
- | - | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,393 | $5,160 |
$4,018
61,822
kWh
|
$375
-
kW-mo/yr
|
- | - | - | |
04 | 2.2442: Preheat combustion air with waste heat | $30,125 | $80,000 | - | - | - |
$30,125
-
MMBtu
|
- | |
05 | 2.1233: Analyze flue gas for proper air/fuel ratio | $4,896 | $15,000 | - | - | - |
$4,896
-
MMBtu
|
- | |
06 | 2.7232: Replace existing hvac unit with high efficiency model | $32,155 | $99,432 |
$30,826
474,240
kWh
|
$1,329
-
kW-mo/yr
|
- | - | - | |
07 | 2.2622: Replace existing chiller with high efficiency model | $33,992 | $200,000 |
$13,344
205,296
kWh
|
$648
-
kW-mo/yr
|
- | - | $20,000 | |
TOTAL RECOMMENDED | $107,767 | $400,052 |
$49,307
758,573
kWh
|
$2,352
-
kW-mo/yr
|
$1,087 |
$35,021
-
MMBtu
|
$20,000 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs