| Assessment Year | 2020 |
|---|---|
| Principal Product | Metal Fabricated Enclosures |
| NAICS | 332999: All Other Miscellaneous Fabricated Metal Product Manufacturing |
| SIC | 3291: Abrasive Products |
| Sales Range | $100 M to 500M |
| # of Employees | 166 |
| Plant Area |
440,000
ft2
|
| Annual Production | 500,000
units
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | New Jersey |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $230,298 | 5,499,608 |
kWh
|
$0.042 |
| Electricity Demand | $74,679 | 13,993 |
kW-mo/yr
|
$5.34 |
| Electricity Fees | $332,394 | - |
|
- |
| Natural Gas | $151,105 | 21,314 |
MMBtu
|
$7.09 |
| TOTAL YEARLY COSTS | $788,476 | |||
| RECOMMENDED SAVINGS* | $53,028 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.8114: Change rate schedules or other changes in utility service | $30,000 | - | - | - | - | $30,000 | |
| 02 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $1,682 | - |
$1,105
26,325
kWh
|
$577
-
kW-mo/yr
|
- | - | |
| 03 | 2.6212: Turn off equipment during breaks, reduce operating time | $3,482 | $3,000 |
$1,955
46,550
kWh
|
$1,527
-
kW-mo/yr
|
- | - | |
| 04 | 2.2437: Recover waste heat from equipment | $3,545 | $5,000 | - | - |
$3,545
-
MMBtu
|
- | |
| 05 | 2.7263: Lower compressor pressure through a/c system modification | $1,393 | $3,150 |
$1,121
26,681
kWh
|
$272
-
kW-mo/yr
|
- | - | |
| 06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,207 | $3,300 |
$977
23,275
kWh
|
$230
-
kW-mo/yr
|
- | - | |
| 07 | 2.7232: Replace existing hvac unit with high efficiency model | $6,578 | $29,000 |
$4,874
116,052
kWh
|
$1,704
-
kW-mo/yr
|
- | - | |
| 08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,991 | $9,200 |
$1,553
36,972
kWh
|
$438
-
kW-mo/yr
|
- | - | |
| 09 | 2.7425: Clean or color roof to reduce solar load | $3,150 | $18,250 |
$1,650
39,285
kWh
|
$2,748
-
kW-mo/yr
|
$(-1,248.0)
-
MMBtu
|
- | |
| TOTAL RECOMMENDED | $53,028 | $70,900 |
$13,235
315,140
kWh
|
$7,496
-
kW-mo/yr
|
$2,297
-
MMBtu
|
$30,000 | ||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs