ITAC Assessment: LE0481
ITAC logo
ITAC Assessment: LE0481
Grant Funding Opportunity NOW OPEN
Up to $300k at 50% cost share for qualifying* projects.
Grant Funding Opportunity Open
Qualifying* small and medium-sized US manufacturers, that received an ITAC, Onsite Energy/CHP TAP, or qualified equivalent assessment since 2018 can now apply for grants for implementation of assessment recommendations at up to 50% of qualifying* project costs with a maximum of $300,000 per grant.
IMPORTANT: The grant program now operates on a rolling basis and applications may be submitted at any time through the year, with quarterly reviews.
*See Full Grant Solicitation for full qualification and selection details.
Assessment Year 2019
Principal Product Vinyl Flooring
NAICS 339999: All Other Miscellaneous Manufacturing
SIC 3999: Manufacturing Industries, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 40
Plant Area 50,000
ft2
Annual Production 1,000,000
units
Production Hrs. Annual 3,744
hrs
Location (State) Pennsylvania

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,074,111 20,300,711
kWh
Electricity Demand $155,025 59,791
kW-mo/yr
Electricity Fees $126,377 -
Natural Gas $819,523 359,548
MMBtu
TOTAL YEARLY COSTS $2,175,036
RECOMMENDED SAVINGS* $137,485 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $78,111

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Ancillary Material Cost Savings
01 2.6212: Turn off equipment during breaks, reduce operating time $7,057 $40 $6,966
131,436
kWh
$91
-
kW-mo/yr
- -
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $13,696 $14,000 $11,842
223,442
kWh
$1,854
-
kW-mo/yr
- -
03 2.2622: Replace existing chiller with high efficiency model $42,460 $57,500 $36,710
692,649
kWh
$5,750
-
kW-mo/yr
- -
04 2.7142: Utilize higher efficiency lamps and/or ballasts $6,547 $11,688 $5,603
105,211
kWh
$837
-
kW-mo/yr
- $107
05 2.5111: Convert from indirect to direct fired systems $50,429 $162,000 - - $50,429
-
MMBtu
-
06 2.7232: Replace existing hvac unit with high efficiency model $842 $3,200 $700
13,200
kWh
$142
-
kW-mo/yr
- -
07 2.4226: Use / purchase optimum sized compressor $13,688 $55,000 $11,834
223,278
kWh
$1,854
-
kW-mo/yr
- -
08 2.2442: Preheat combustion air with waste heat $2,376 $10,000 - - $2,376
-
MMBtu
-
09 2.2437: Recover waste heat from equipment $390 $1,850 - - $390
-
MMBtu
-
TOTAL RECOMMENDED $137,485 $315,278 $73,655
1,389,216
kWh
$10,528
-
kW-mo/yr
$53,195
-
MMBtu
$107
TOTAL IMPLEMENTED $78,111 $230,578 $24,403
459,925
kWh
$2,782
-
kW-mo/yr
$50,819
-
MMBtu
$107
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Ancillary Material Cost Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs