Assessment Year | 2019 |
---|---|
Principal Product | Vinyl Flooring |
NAICS | 339999: All Other Miscellaneous Manufacturing |
SIC | 3999: Manufacturing Industries, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 40 |
Plant Area |
50,000
ft2
|
Annual Production | 1,000,000
units
|
Production Hrs. Annual | 3,744
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,074,111 | 20,300,711 |
kWh
|
$0.053 |
Electricity Demand | $155,025 | 59,791 |
kW-mo/yr
|
$2.59 |
Electricity Fees | $126,377 | - |
|
- |
Natural Gas | $819,523 | 359,548 |
MMBtu
|
$2.28 |
TOTAL YEARLY COSTS | $2,175,036 | |||
RECOMMENDED SAVINGS* | $137,485 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $78,111 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6212: Turn off equipment during breaks, reduce operating time | $7,057 | $40 |
$6,966
131,436
kWh
|
$91
-
kW-mo/yr
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $13,696 | $14,000 |
$11,842
223,442
kWh
|
$1,854
-
kW-mo/yr
|
- | - | |
03 | 2.2622: Replace existing chiller with high efficiency model | $42,460 | $57,500 |
$36,710
692,649
kWh
|
$5,750
-
kW-mo/yr
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,547 | $11,688 |
$5,603
105,211
kWh
|
$837
-
kW-mo/yr
|
- | $107 | |
05 | 2.5111: Convert from indirect to direct fired systems | $50,429 | $162,000 | - | - |
$50,429
-
MMBtu
|
- | |
06 | 2.7232: Replace existing hvac unit with high efficiency model | $842 | $3,200 |
$700
13,200
kWh
|
$142
-
kW-mo/yr
|
- | - | |
07 | 2.4226: Use / purchase optimum sized compressor | $13,688 | $55,000 |
$11,834
223,278
kWh
|
$1,854
-
kW-mo/yr
|
- | - | |
08 | 2.2442: Preheat combustion air with waste heat | $2,376 | $10,000 | - | - |
$2,376
-
MMBtu
|
- | |
09 | 2.2437: Recover waste heat from equipment | $390 | $1,850 | - | - |
$390
-
MMBtu
|
- | |
TOTAL RECOMMENDED | $137,485 | $315,278 |
$73,655
1,389,216
kWh
|
$10,528
-
kW-mo/yr
|
$53,195
-
MMBtu
|
$107 | ||
TOTAL IMPLEMENTED | $78,111 | $230,578 |
$24,403
459,925
kWh
|
$2,782
-
kW-mo/yr
|
$50,819
-
MMBtu
|
$107 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs