Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $489,992 | 7,615,200 |
kWh
|
$0.064 |
Electricity Demand | $41,346 | 16,234 |
kW-mo/yr
|
$2.55 |
Electricity Fees | $12,132 | - |
|
- |
Natural Gas | $1,103,800 | 313,122 |
MMBtu
|
$3.53 |
TOTAL YEARLY COSTS | $1,647,270 | |||
RECOMMENDED SAVINGS* | $639,375 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $159,828 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6122: Adjust vents to minimize energy use | $43,794 | - |
$(-5,729.0)
(-89,520)
kWh
|
$(-477.0)
-
kW-mo/yr
|
- | $50,000 | |
02 | 2.2113: Repair or replace steam traps | $19,944 | $1,143 | - | - |
$19,944
-
MMBtu
|
- | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $96,090 | $12,000 |
$95,899
1,498,425
kWh
|
$191
-
kW-mo/yr
|
- | - | |
04 | 2.2511: Insulate bare equipment | $2,802 | $750 |
$2,802
43,788
kWh
|
- | - | - | |
05 | 2.2442: Preheat combustion air with waste heat | $401,509 | $120,000 | - | - |
$401,509
-
MMBtu
|
- | |
06 | 2.5125: Size air handling grills/ duct/s coils to minimize air resistance | $14,597 | $17,000 |
$13,513
211,144
kWh
|
$1,084
-
kW-mo/yr
|
- | - | |
07 | 2.1233: Analyze flue gas for proper air/fuel ratio | $48,028 | $55,800 | - | - |
$48,028
-
MMBtu
|
- | |
08 | 2.7261: Install timers and/or thermostats | $12,611 | $28,000 |
$10,344
161,629
kWh
|
$2,267
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $639,375 | $234,693 |
$116,829
1,825,466
kWh
|
$3,065
-
kW-mo/yr
|
$469,481
-
MMBtu
|
$50,000 | ||
TOTAL IMPLEMENTED | $159,828 | $13,143 |
$90,170
1,408,905
kWh
|
$(-286.0)
-
kW-mo/yr
|
$19,944
-
MMBtu
|
$50,000 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs