Assessment Year | 2019 |
---|---|
Principal Product | Electrical Connectors |
NAICS | 334417: Electronic Connector Manufacturing |
SIC | 3678: Electronic Connectors |
Sales Range | $10 M to 50M |
# of Employees | 38 |
Plant Area |
86,000
ft2
|
Annual Production | 10,000,000
units
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $117,991 | 1,952,626 |
kWh
|
$0.060 |
Electricity Demand | $20,735 | 4,983 |
kW-mo/yr
|
$4.16 |
Electricity Fees | $21,735 | - |
|
- |
Natural Gas | $9,141 | 1,905 |
MMBtu
|
$4.80 |
TOTAL YEARLY COSTS | $169,602 | |||
RECOMMENDED SAVINGS* | $44,333 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $12,803 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.6212: Turn off equipment during breaks, reduce operating time | $9,240 | - |
$8,058
134,307
kWh
|
$1,182
-
kW-mo/yr
|
|
02 | 2.4221: Install compressor air intakes in coolest locations | $1,177 | $2,000 |
$1,040
17,323
kWh
|
$137
-
kW-mo/yr
|
|
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,128 | $10,000 |
$2,828
47,131
kWh
|
$300
-
kW-mo/yr
|
|
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,513 | $12,830 |
$3,064
51,074
kWh
|
$449
-
kW-mo/yr
|
|
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $50 | $200 |
$50
838
kWh
|
- | |
06 | 2.4226: Use / purchase optimum sized compressor | $11,265 | $46,000 |
$9,892
164,866
kWh
|
$1,373
-
kW-mo/yr
|
|
07 | 2.7232: Replace existing hvac unit with high efficiency model | $13,604 | $56,575 |
$11,807
196,785
kWh
|
$1,797
-
kW-mo/yr
|
|
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $2,356 | $15,000 |
$2,077
34,622
kWh
|
$279
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $44,333 | $142,605 |
$38,816
646,946
kWh
|
$5,517
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $12,803 | $13,030 |
$11,172
186,219
kWh
|
$1,631
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs