Assessment Year | 2018 |
---|---|
Principal Product | Thermoformed Plastic Trays |
NAICS | 326112: Plastics Packaging Film and Sheet (including Laminated) Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 109 |
Plant Area |
62,500
ft2
|
Annual Production | 265,000,000
units
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $414,294 | 8,577,509 |
kWh
|
$0.048 |
Electricity Demand | $64,137 | 21,595 |
kW-mo/yr
|
$2.97 |
Electricity Fees | $111,089 | - |
|
- |
Natural Gas | $18,997 | 1,965 |
MMBtu
|
$9.67 |
TOTAL YEARLY COSTS | $608,517 | |||
RECOMMENDED SAVINGS* | $84,413 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $11,918 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,416 | $1,000 |
$4,840
100,826
kWh
|
$576
-
kW-mo/yr
|
|
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,502 | $19,292 |
$5,811
121,056
kWh
|
$691
-
kW-mo/yr
|
|
03 | 2.7232: Replace existing hvac unit with high efficiency model | $15,594 | $73,000 |
$13,991
291,470
kWh
|
$1,603
-
kW-mo/yr
|
|
04 | 2.2622: Replace existing chiller with high efficiency model | $47,928 | $260,000 |
$42,831
892,320
kWh
|
$5,097
-
kW-mo/yr
|
|
05 | 2.4226: Use / purchase optimum sized compressor | $8,973 | $50,000 |
$8,020
167,080
kWh
|
$953
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $84,413 | $403,292 |
$75,493
1,572,752
kWh
|
$8,920
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $11,918 | $20,292 |
$10,651
221,882
kWh
|
$1,267
-
kW-mo/yr
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs