Assessment Year | 2018 |
---|---|
Principal Product | Architectural Glazing Systems |
NAICS | 332321: Metal Window and Door Manufacturing |
SIC | 3442: Metal Doors, Sash, Frames, Molding, and Trim Manufacturing |
Sales Range | $10 M to 50M |
# of Employees | 33 |
Plant Area |
290,000
ft2
|
Annual Production | 707
units
|
Production Hrs. Annual | 3,120
hrs
|
Location (State) | Pennsylvania |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $118,746 | 1,554,200 |
kWh
|
$0.076 |
Electricity Demand | $25,583 | 6,608 |
kW-mo/yr
|
$3.87 |
Electricity Fees | $5,400 | - |
|
- |
LPG | $40,214 | 3,671 |
MMBtu
|
$10.95 |
TOTAL YEARLY COSTS | $189,943 | |||
RECOMMENDED SAVINGS* | $45,718 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $15,830 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
---|---|---|---|---|---|---|---|
01 | 2.7261: Install timers and/or thermostats | $2,899 | $25 |
$1,912
25,160
kWh
|
- |
$986
-
MMBtu
|
|
02 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,450 | $25 |
$1,372
18,058
kWh
|
$77
-
kW-mo/yr
|
- | |
03 | 2.7232: Replace existing hvac unit with high efficiency model | $14,206 | $20,625 |
$13,544
178,214
kWh
|
$662
-
kW-mo/yr
|
- | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,228 | $19,000 |
$9,452
124,363
kWh
|
$1,776
-
kW-mo/yr
|
- | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $874 | $1,500 |
$754
9,915
kWh
|
$120
-
kW-mo/yr
|
- | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,660 | $5,250 |
$1,660
21,840
kWh
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,721 | $11,738 |
$2,276
29,952
kWh
|
$445
-
kW-mo/yr
|
- | |
08 | 2.2441: Preheat boiler makeup water with waste process heat | $6,258 | $30,000 | - | - |
$6,258
-
MMBtu
|
|
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $843 | $4,225 |
$696
9,152
kWh
|
$147
-
kW-mo/yr
|
- | |
10 | 2.7261: Install timers and/or thermostats | $3,580 | $20,000 |
$1,158
15,238
kWh
|
- |
$2,422
-
MMBtu
|
|
TOTAL RECOMMENDED | $45,718 | $112,388 |
$32,824
431,892
kWh
|
$3,228
-
kW-mo/yr
|
$9,667
-
MMBtu
|
||
TOTAL IMPLEMENTED | $15,830 | $51,263 |
$7,916
104,162
kWh
|
$670
-
kW-mo/yr
|
$7,245
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | LPG Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs